Furman ASD-120 2.0 Скачать руководство пользователя страница 16

15

LOCAL AND REMOTE OPERATING MODES       

Other configuration options are possible with an understanding of the REMOTE in-
terface and configuration features of the ASD-120 2.0 discussed in the following 
sections. 

Key Switch Control

Secured local control of the ASD-120 2.0 is best accomplished by using the 
front panel Key Switch.  When in the ON position, all Delay Banks will sequence 
ON, except those configured with the Bypass Set as Always OFF.  All Banks not 
configured as Always ON will be switched OFF once the Key Switch is returned to 
the OFF position. If the Key Switch is intended to be the primary control method, 
no external control connection to the rear panel REMOTE interface REM terminal 
is recommended, and DIP 6 should be set to the GND ON position (DIP 6 UP).  In 
the absence of any external control signal, once the key switch has initially been 
rotated to the ON position and returned to the REMOTE position, the ASD-120 2.0 
defaults to ON in either Maintained Mode or Momentary Mode.  

Note:

:  The front panel Key Switch must be in the REMOTE position for ASD-120 

2.0 to accept remote commands. Furthermore, an ON or an OFF key position set-
ting functions in either DIP 7 Maintained or Momentary mode effectively bypasses 
all other command functions except the Bypass Set or a FORCE OFF condition.

Note:

  The Start Sequence Button is disabled when DIP 6 is in GND ON mode 

(Position UP).

Note:

  Loss of AC Power or utility interruption in Maintained Mode will result in 

all Banks returning to the previous programmed state when the utility service is 
restored.  Maintained On, Banks will return to ON.  Maintained OFF, Banks will 
return to OFF.   

Note:

  Loss of AC Power or utility interruption in Momentary Mode will result in all 

Banks returning to an OFF state when the utility service is restored. 

Front Panel Start Sequence Button Control   

The ASD-120 2.0 front panel Start Sequence button can be used as the primary 
control to initiate a sequence.  If the unit is programmed for Momentary Mode 
(DIP 7 = ON), each time Start Sequence is depressed, the ASD-120 2.0 will tog-
gle between ON and OFF sequences.  If the button is pressed and held for more 
than six seconds, the ASD-120 2.0 will sequence to the OFF state.  

The front Start Sequence button should only be used when the Key Switch is in 
the REMOTE position with DIP 7 the MOM/MNT dip switch set to MOM (DIP 7 in 
the UP position).

Push buttons in multiple locations can be used to initiate ON/OFF sequences.  
Remote control options are discussed in the Momentary Mode Section.

Note:

  The Start Sequence Button is disabled when DIP 6 is in GND ON mode 

(Position UP).

Note:

  Loss of AC Power in Momentary Mode will result in all Banks returning to 

an OFF state when the utility service is restored. 

Remote Operating Modes

When the Key Switch is in the REMOTE position, the ASD-120 2.0 will respond as 
configured by the switches behind the front panel cover plate.  The ASD-120 2.0 
can be programmed to respond to remote Momentary and sustained (Maintained) 
trigger conditions.  The unit can be triggered by the presence or absence of 
contact closures or a DC voltage.  The ASD-120 2.0 can also be used to trigger 
remote equipment using the same type of trigger conditions.

The ASD-120 2.0 and similar equipment (available from FURMAN and other 
sources) can be controlled in parallel with a control signal wired from a single 
switch.  Also, control connections can be made in series with various units trig-
gered from an event occurring at another piece of equipment.  An infinite variety 
of connection schemes using any combination of these two methods is possible.  

The momentary mode is only used with trigger signals that are of a short duration 
such as a push button.  Equipment compatible with this type of trigger can be 
connected in a way that permits the initialization of a sequence from push buttons 
in multiple locations.

Signal level relay contacts A thru F are provided at the rear panel of the ASD-120 
2.0 which can be used for the purpose of triggering external equipment.  The 
contacts can be configured as a group as normally open (NO) or normally 
closed (NC).

When the key switch is in either the ON or OFF position, the ASD-120’s sequenc-
ing circuits will not respond to the rear panel remote control inputs. If the key 
switch is returned to the REMOTE position, the signals supplied to the rear panel 
remote inputs will again control the unit.

Содержание ASD-120 2.0

Страница 1: ...PUT 120 3 208 240 VAC 14400 WATTS 120 AMPS MAX 20A MAX DELAY A 20A MAX DELAY B 20A MAX DELAY C 20A MAX DELAY D 20A MAX DELAY E 20A MAX DELAY F FORCE OFF DELAY OUTPUTS REMOTE NC A B C D E F NO 12V STAT...

Страница 2: ...ET CONFIER LA MAINTENANCE A UN T ECHNICIEN QUALIFIE DRY RELAY CONTACTS RATING 48V 1 AMP This box should include the following items 1 Model ASD 120 2 0 2 Two adjustable rear rack mounting ears 3 Secu...

Страница 3: ...ASD 120 2 0 please use the Direct Current 12V and REM terminals of the ASD 120 2 0 to provide the DC control signal to the REM input of the older ASD 120 product Ground loops at the control terminals...

Страница 4: ...ND If the loads are balanced the neutral cur rent will be zero but if the load is predominately on one phase the neutral must support the entire load current Since phases are distributed to different...

Страница 5: ...ENCE REMOTE DLY ADJ DELAY A DELAY B DELAY C PHASE X Y Z DELAY D DELAY E DELAY F OFF ON 1 2 3 4 5 6 7 ALWAYS ON ALWAYS OFF ASD 120 2 0 120 AMP POWER SEQUENCER SEE COVER PLATE START SEQUENCE REMOTE DLY...

Страница 6: ...AY F OFF ON ASD 120 2 0 120 AMP POWER SEQUENCER Security Cover to Protect Program Settings 1 5 Cable Clamp Input 120V Phase Six 20A duplex outlets Force Off 2 Pin Phoenix type Connector Remote 4 pin P...

Страница 7: ...ower of 14 4kW Higher levels of power can be achieved by connecting additional Furman sequencers or other power conditioning products including additional ASD 120 2 0 units Furman products provide a p...

Страница 8: ...l of the Delay Bank LEDs should be off Note that the Delay Bank LED indicators only indicate when a bank has been activated The indicators do not guarantee that power is being delivered to the corresp...

Страница 9: ...ector and the front panel START SEQUENCE push button switch Security Cover Shield and DIP Switch Program Interface The ASD 120 2 0 had two configuration DIP switches that are located underneath a secu...

Страница 10: ...1 minute maximum time delay DIP 2 adds 2 minutes and DIP 3 adds 4 minutes Please note these time delays are cumulative If all three DIP switches are in the UP position the maximum allowable time delay...

Страница 11: ...at once once any Momentary switch button is pushed including Remote Momentary switches As mentioned multiple momen tary remote contacts should be used if more than one remote power up location is des...

Страница 12: ...tary Maintained Sets local mode and remote contact closure preference for either Momentary or Maintained switches Note Momentary mode overrides DIP 5 and 6 Sequence Bypass DIP Switch DIP position ON A...

Страница 13: ...0 Delay outlets are OFF To use the STAT terminal output simply connect an LED between the STAT and GND with the Cathode flat side of the LED oriented toward the GND pin Pin 4 Do not use a series curr...

Страница 14: ...e set to OFF A time delayed On or Off sequence can be initiated at the front panel Key Switch the START SEQUENCE button or using the 4 Pin Remote Interface The config uration Multi Function DIP switch...

Страница 15: ...using external 5 to 30VDC power supply In this mode an external power supply will prevent the ASD 120 2 0 from sequencing ON The ASD 120 2 0 will automatically sequence ON when the DC power is remove...

Страница 16: ...uences If the button is pressed and held for more than six seconds the ASD 120 2 0 will sequence to the OFF state The front Start Sequence button should only be used when the Key Switch is in the REMO...

Страница 17: ...state until a connection is present between the REM and GND terminals or between the 12V and REM terminals DIP 7 switch is set in the down position MNT for operation in Maintained Mode And when utiliz...

Страница 18: ...ate of the DC relay as well as its associated AC duplex FORCE OFF Interface Rear Panel 2 pin Connector The FORCE OFF input provides a method of immediately turning off all Bank relays and output circu...

Страница 19: ...ry Mode DIP 4 UP NO verify factory default DIP 7 UP MOM verify Momentary Mode Configure 2 0 Multi Function DIP switches 1 2 3 to desired delay time interval Ensure All Bypass Set DIP switches are sele...

Страница 20: ...Delay Banks A through F Diagram Example 4 A Furman M 8S Sequencer triggered by an optional RS 1 Remote System Control Panel activates a Furman ASD 120 2 0 Sequencers at another in house location Diagr...

Страница 21: ...SD 120 2 0 ADVANCED INSTALLATION WITH FURMAN CN SERIES AND REMOTE RS 1 SWITCH ON ON CN 2400S DIP SETTINGS ASD 120 2 0 DIP SETTINGS FIRE ALARM NO C NC FORCE REMOTE 12V STAT REM GND 12V STAT REM GND DLY...

Страница 22: ...rs one per output Configuration Switches Front panel hidden by security cover 3 maximum delay switches 1 2 and 4 minute Force Off NO NC 12V mode On Off GND mode On Off Momentary Maintained mode select...

Страница 23: ...orce and effect SERVICE NOTE All equipment being returned for repair must have an RMA Return Mate rials Authorization number To receive an RMA number please contact Furman Technical Services at techsu...

Страница 24: ...y the GND ON Maintained Mode should be used Note GND to REM pins should be used for remote triggers with applied DC voltages 5V to 30VDC at REM ASD 120 2 0 PROGRAMMING SUMMARY DIP 7 MOM MNT Maintained...

Отзывы: