Furman ASD-120 2.0 Скачать руководство пользователя страница 11

10

DIP Switch position #6 (Factory default is OFF)

DIP Switch position 6 defines how the ASD-120 2.0 will behave when GND is ap-
plied to the REM pin on the Remote interface.  If this switch is in the ON position, 
the ASD-120 2.0 will sequence ON when GND is applied to the REM input.  If this 
switch is in the OFF position the ASD-120 2.0will follow the behavior defined by 
DIP Switch #5.  DIP switch 7 must be in the OFF position (Maintained mode).

DIP Switch position #7 (Factory default is OFF)

DIP Switch position 7 defines the switching preference for switches or devices 
connected to the REM pin on the Remote Interface.  If this switch is in the ON 
position, the ASD-120 2.0 will operate in Momentary mode.  If this switch is in the 
OFF position the product will operate in Maintained mode.

Maintained switches, for example toggle switches or push-ON / push-OFF push 
button latching switches maintain their contact position until the switch is actuat-
ed a second time.  Thus a switch that is closed will remain closed until the switch 
position is changed (such as the Furman RS-1).

 

The ASD-120 2.0 has one Momentary Mode of operation (DIP 7 ON or UP), 
which is also compatible with Furman Legacy products. As suggested, when 
more than one remote switching location is required, momentary switches offer 
an advantage. In addition to this benefit, multiple Primary units set to Momentary 
Mode can be interfaced together using the Remote Pole co12V, REM and 
GND, wired in parallel pole to pole. No one unit is considered the Primary Unit, yet 
any unit can act as one. The multiple units’ delay cycle would initiate at the same 
time, in combination with each other; in other words, the units would all start at 
once and all initiate a cycle down at once, once any Momentary switch (button) is 
pushed (including Remote Momentary switches). As mentioned, multiple momen-
tary remote contacts should be used if more than one remote power up location 
is desired. If units should drop out of sync, simply press and hold down the Start 
Sequence button for several seconds to re-sync. 

A front panel position DIP switch is used to set the sequence mode (+12V 
ON, +12V OFF, GND ON, Mom/ Maint) which defines how the ASD-120 2.0 will 

react to the signal presented on its REM input.  The table below summarizes the 
behavior which is described in further detail below. Note that DIP switch position 
6 overrides the setting of DIP switch 5, and DIP switch 7 overrides switches 5 
and 6.

Note: The front panel START SEQUENCE switch is only active when the Key Switch is in the 
REMOTE Position
Sequences the ASD-120 2.0 ON when REM = Open Circuit
Sequences the ASD-120 2.0 OFF when REM = 12VDC
Sequences the ASD-120 2.0 ON when REM = 12VDC
Sequences the ASD-120 2.0 OFF when REM = Open Circuit

Sequences the ASD-120 2.0 ON when REM is connected to GND terminal
Sequences the ASD-120 2.0 OFF when REM = Open Circuit

Sequences the ASD-120 2.0 from ON to OFF or OFF to ON each time +12V is applied to the REM input.

DIP 5

12V ON
OFF

ON

OFF

ON

OFF

ON

OFF

ON

DIP 6

GND ON
OFF

OFF

ON

ON

OFF

OFF

ON

ON

DIP 7

MOM/MNT
OFF

OFF

OFF

OFF

ON

ON

ON

ON

MODE

+12V OFF

+12V ON

GND ON

GND ON

Momentary

Momentary

Momentary

Momentary

DIP #s

5  6  7

FACTORY DEFAULT SETTING

DIP Switch position #5 (Factory default is OFF)

DIP Switch position 5 defines how the ASD-120 2.0 will behave when +12VDC is 
applied to the REM pin on the Remote interface.  If this switch is in the ON posi-
tion, the ASD-120 2.0 will sequence ON when +12V is applied to the REM input.  
If this switch is in the OFF position (+12V OFF) the ASD-120 2.0 will sequence 

OFF when +12V is applied to the REM input.  DIP switches 6 and 7 must be in 
the OFF position (Maintained mode).

Содержание ASD-120 2.0

Страница 1: ...PUT 120 3 208 240 VAC 14400 WATTS 120 AMPS MAX 20A MAX DELAY A 20A MAX DELAY B 20A MAX DELAY C 20A MAX DELAY D 20A MAX DELAY E 20A MAX DELAY F FORCE OFF DELAY OUTPUTS REMOTE NC A B C D E F NO 12V STAT...

Страница 2: ...ET CONFIER LA MAINTENANCE A UN T ECHNICIEN QUALIFIE DRY RELAY CONTACTS RATING 48V 1 AMP This box should include the following items 1 Model ASD 120 2 0 2 Two adjustable rear rack mounting ears 3 Secu...

Страница 3: ...ASD 120 2 0 please use the Direct Current 12V and REM terminals of the ASD 120 2 0 to provide the DC control signal to the REM input of the older ASD 120 product Ground loops at the control terminals...

Страница 4: ...ND If the loads are balanced the neutral cur rent will be zero but if the load is predominately on one phase the neutral must support the entire load current Since phases are distributed to different...

Страница 5: ...ENCE REMOTE DLY ADJ DELAY A DELAY B DELAY C PHASE X Y Z DELAY D DELAY E DELAY F OFF ON 1 2 3 4 5 6 7 ALWAYS ON ALWAYS OFF ASD 120 2 0 120 AMP POWER SEQUENCER SEE COVER PLATE START SEQUENCE REMOTE DLY...

Страница 6: ...AY F OFF ON ASD 120 2 0 120 AMP POWER SEQUENCER Security Cover to Protect Program Settings 1 5 Cable Clamp Input 120V Phase Six 20A duplex outlets Force Off 2 Pin Phoenix type Connector Remote 4 pin P...

Страница 7: ...ower of 14 4kW Higher levels of power can be achieved by connecting additional Furman sequencers or other power conditioning products including additional ASD 120 2 0 units Furman products provide a p...

Страница 8: ...l of the Delay Bank LEDs should be off Note that the Delay Bank LED indicators only indicate when a bank has been activated The indicators do not guarantee that power is being delivered to the corresp...

Страница 9: ...ector and the front panel START SEQUENCE push button switch Security Cover Shield and DIP Switch Program Interface The ASD 120 2 0 had two configuration DIP switches that are located underneath a secu...

Страница 10: ...1 minute maximum time delay DIP 2 adds 2 minutes and DIP 3 adds 4 minutes Please note these time delays are cumulative If all three DIP switches are in the UP position the maximum allowable time delay...

Страница 11: ...at once once any Momentary switch button is pushed including Remote Momentary switches As mentioned multiple momen tary remote contacts should be used if more than one remote power up location is des...

Страница 12: ...tary Maintained Sets local mode and remote contact closure preference for either Momentary or Maintained switches Note Momentary mode overrides DIP 5 and 6 Sequence Bypass DIP Switch DIP position ON A...

Страница 13: ...0 Delay outlets are OFF To use the STAT terminal output simply connect an LED between the STAT and GND with the Cathode flat side of the LED oriented toward the GND pin Pin 4 Do not use a series curr...

Страница 14: ...e set to OFF A time delayed On or Off sequence can be initiated at the front panel Key Switch the START SEQUENCE button or using the 4 Pin Remote Interface The config uration Multi Function DIP switch...

Страница 15: ...using external 5 to 30VDC power supply In this mode an external power supply will prevent the ASD 120 2 0 from sequencing ON The ASD 120 2 0 will automatically sequence ON when the DC power is remove...

Страница 16: ...uences If the button is pressed and held for more than six seconds the ASD 120 2 0 will sequence to the OFF state The front Start Sequence button should only be used when the Key Switch is in the REMO...

Страница 17: ...state until a connection is present between the REM and GND terminals or between the 12V and REM terminals DIP 7 switch is set in the down position MNT for operation in Maintained Mode And when utiliz...

Страница 18: ...ate of the DC relay as well as its associated AC duplex FORCE OFF Interface Rear Panel 2 pin Connector The FORCE OFF input provides a method of immediately turning off all Bank relays and output circu...

Страница 19: ...ry Mode DIP 4 UP NO verify factory default DIP 7 UP MOM verify Momentary Mode Configure 2 0 Multi Function DIP switches 1 2 3 to desired delay time interval Ensure All Bypass Set DIP switches are sele...

Страница 20: ...Delay Banks A through F Diagram Example 4 A Furman M 8S Sequencer triggered by an optional RS 1 Remote System Control Panel activates a Furman ASD 120 2 0 Sequencers at another in house location Diagr...

Страница 21: ...SD 120 2 0 ADVANCED INSTALLATION WITH FURMAN CN SERIES AND REMOTE RS 1 SWITCH ON ON CN 2400S DIP SETTINGS ASD 120 2 0 DIP SETTINGS FIRE ALARM NO C NC FORCE REMOTE 12V STAT REM GND 12V STAT REM GND DLY...

Страница 22: ...rs one per output Configuration Switches Front panel hidden by security cover 3 maximum delay switches 1 2 and 4 minute Force Off NO NC 12V mode On Off GND mode On Off Momentary Maintained mode select...

Страница 23: ...orce and effect SERVICE NOTE All equipment being returned for repair must have an RMA Return Mate rials Authorization number To receive an RMA number please contact Furman Technical Services at techsu...

Страница 24: ...y the GND ON Maintained Mode should be used Note GND to REM pins should be used for remote triggers with applied DC voltages 5V to 30VDC at REM ASD 120 2 0 PROGRAMMING SUMMARY DIP 7 MOM MNT Maintained...

Отзывы: