- (OU01 - 04) -
Outdoor unit / 3 phase
O
U
T
D
O
O
R U
N
IT
WO
K1
1
2
-1
6
0
L
C
T
A
O
U
T
D
O
O
R U
N
IT
WO
K1
1
2
-1
6
0
L
C
T
A
SPECIFICATIONS
21
NOMINAL CAPACITY AND NOMINAL INPUT
2-11
* Test conditions comply with EN14511-2
Model name (Outdoor unit)
WO
Û
K112LCTA
WO
Û
K140LCTA
WO
Û
K160LCTA
POWER SOURCE
3Ø 400V ~ 50Hz
+7°C/+35°C
floor heating
Heating capacity
Minimum
kW
6.20
6.20
6.20
Nominal
10.80
13.50
15.17
Maximum
19.50
21.00
22.00
Input power
Nominal
2.51
3.20
3.70
COP
-
4.30
4.22
4.10
+7°C/+45°C
radiators
Heating capacity
Nominal
kW
9.90
12.10
12.75
Input power
2.98
3.78
3.97
COP
-
3.32
3.20
3.21
+2°C/+35°C
floor heating
Heating capacity
Nominal
kW
10.77
13.00
13.50
Input power
3.40
4.15
4.34
COP
-
3.17
3.13
3.11
Содержание Waterstage WOYG140LCTA
Страница 21: ... OU01 16 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LF OUTDOOR UNIT WO A060 100LF MODEL WO A080LFCA ...
Страница 22: ... OU01 17 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LF OUTDOOR UNIT WO A060 100LF MODEL WO A100LFTA ...
Страница 36: ...1 OUTDOOR UNIT DTW_1SP006E_01 CHAPTER01 2018 02 18 SINGLE PHASE TYPE WO G112LCTA WO G140LCTA ...
Страница 64: ...1 OUTDOOR UNIT DTW_3SP003E_01 CHAPTER01 2016 02 18 3 PHASE TYPE WO K112LCTA WO K140LCTA WO K160LCTA ...
Страница 199: ... CS01 83 Control system CS01 83 CONTROL SYSTEM CONTROL SYSTEM ...