SPECIFICATIONS
21
NOMINAL CAPACITY AND NOMINAL INPUT
2-11
Model name (Outdoor unit)
WO
Û
G112LCTA
WO
Û
G140LCTA
POWER SOURCE
1Ø 230V.~ 50Hz
+7°C/+35°C
floor heating
Heating capacity
Minimum
kW
6.20
6.20
Nominal
10.80
13.50
Maximum
16.70
19.60
Input power
Nominal
2.54
3.23
COP
-
4.25
4.18
+7°C/+45°C
radiators
Heating capacity
Nominal
kW
9.05
11.32
Input power
2.82
3.69
COP
-
3.21
3.07
+2°C/+35°C
floor heating
Heating capacity
Nominal
kW
10.77
12.00
Input power
3.44
3.87
COP
-
3.13
3.10
* Test conditions comply with EN14511-2