- (CS01 - 13) -
Control system
- (CS01 - 13) -
C
O
N
T
R
O
L
SY
S
T
E
M
C
O
N
T
R
O
L
SY
S
T
E
M
LINE
ACCESS
LEVEL
FUNCTION
SETTING RANGE
OR DISPLAY
FACTORY
SETTING
760
S
Room temp limitation
0.5…4°C
0.5°C
As soon as the room temperature = [Setpoint line 710 (ex. 20°C) + Room temperature
limitation setpoint line 760 (ex. 0.5 °C)] > 20.5 °C => The heat pump is stopped.
It restarts when the room temperature falls below the setpoint (in the example, Room
temperature < 20,0 °C).
780
S
Quick setback
Off
Down to reduced setpoint
Down to frost prot setpoint
Off
790
S
Optimum start control max
0…360min
180 min
791
S
Optimum stop control max
0…360min
30 min
800
S
Reduced setpoint increase start
-30…10°C
---°C
801
S
Reduced setpoint increase end
-30…10°C
-5°C
830
S
Mixer valve boost
0…50°C
0°C
834
S
Actuator running time
30…873s
240s
850
I
Floor curing function
Off
- Off: Early interruption of the current programme, programme inactive.
- Operational heating.
- Heating ready for occupation.
- Operational h ready heating.
- Ready h operational heating.
- Manual: Manual mode enables you to programme your own concrete slab drying time.
The function ends automatically after 25 days.
851
I
Floor curing setpoint manually
0…95°C
25°C
This function enables you to set the custom concrete slab drying temperature. This
temperature remains fixed.
The concrete slab-drying programme stops automatically after running for 25 days.
856
I
Floor curing day current
0...32
857
I
Floor curing days completed
0...32
900
S
Operating mode changeover
None, Protection mode,
Reduced, Comfort,
Automatic
Reduced
Operating mode at end of concrete slab drying period.
Cooling circuit 1
901
U
Operating mode
Protection, Automatic,
Reduced,Comfort
Protection
902
U
Comfort cooling setpoint
17…40°C
24°C
903
U
Reduced setpoint
5... 40°C
26°C
908
I
Flow temp setpoint at OT 25°C
6... 35°C
20°C
909
I
Flow temp setpoint at OT 35°C
6... 35°C
16°C
912
I
Cooling limit at OT
8... 35°C
24°C
913
S
Lock time at end of heating / cooling
8... 100h
24h
918
S
Summer compensation start at OT
20…50°C
26°C
919
S
Summer compensation end at OT
20…50°C
40°C
920
S
Summer compensation setpoint
increase
1... 10 °C
4°C
923
S
Flow temp setpoint min OT 25°C
6…35°C
18°C
924
S
Flow temp setpoint min OT 35°C
6…35°C
18°C
928
S
Room influence
1…100%
80%
932
S
Room temp limitation
0,5... 4 °C
0.5°C
938
S
Mixing valve decrease
0…20°C
0°C
941
S
Actuator running time
30…873s
240s
963
S
With primary controller/system pump
No, Yes
No*
*Basic setting : 1 circuit = No ; 2 circuits = Yes.
Содержание Waterstage WOYG140LCTA
Страница 21: ... OU01 16 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LF OUTDOOR UNIT WO A060 100LF MODEL WO A080LFCA ...
Страница 22: ... OU01 17 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LF OUTDOOR UNIT WO A060 100LF MODEL WO A100LFTA ...
Страница 36: ...1 OUTDOOR UNIT DTW_1SP006E_01 CHAPTER01 2018 02 18 SINGLE PHASE TYPE WO G112LCTA WO G140LCTA ...
Страница 64: ...1 OUTDOOR UNIT DTW_3SP003E_01 CHAPTER01 2016 02 18 3 PHASE TYPE WO K112LCTA WO K140LCTA WO K160LCTA ...
Страница 199: ... CS01 83 Control system CS01 83 CONTROL SYSTEM CONTROL SYSTEM ...