Simulation
LINE
FUNCTION
7150
Simulation outside temp
Simulation outside temp
To make the starting-up and troubleshooting
processes easier, it is possible to simulate an
outdoor temperature in the range of -50...+50°C.
During simulation, the current, composite and
attenuated outdoor temperatures are ignored
and substituted with the adjusted simulation
temperature.
Computation of the three outdoor temperatures
based on the actual outdoor temperature continues
to be performed during the simulation, and these
temperatures are available again when the
simulation is over.
This function can be deactivated by selecting -.- on
this line or automatically, after a 5 hour waiting
period.