- (CS01 - 28) -
Control system
- (CS01 - 28) -
C
O
N
T
R
O
L
SY
S
T
E
M
C
O
N
T
R
O
L
SY
S
T
E
M
Quick setback
LINE
FUNCTION
760
1060
Room temp limitation
780
1080
Quick setback
Room temp limitaion
The "Room temperature limitation" function enables
the heating circuit pump to be deactivated should
the room temperature exceed the current room
temperature setpoint by more than the adjusted
differential.
The heating circuit pump is activated again as soon
as the room temperature falls to a level below the
current room temperature setpoint.
During the time the "Room temperature limitation"
function is active, no heat request is sent to the
producer.
Quick setback
During quick setback, the heating circuit pump is
deactivated and, in the case of mixing circuits, the
mixing valve is fully closed.
When using a room sensor, the function keeps the
heating off until the room temperature drops to the
level of the "Reduced" or "Frost protection" setpoint.
If the room temperature falls to the reduced or frost
level, the heating circuit pump is activated and the
mixing valve released.
Quick setback switches the heating off for a certain
period of time, depending on the outside
temperature
and the building time constant.
Duration of quick setback when "Comfort" setpoint
minus "Reduced" setpoint = 2 K (e.g. "Comfort"
setpoint = 20 °C and "Reduced" setpoint = 18 °C)
°C
TRx
TRw+SDR
TRw
T
ON
P
OFF
TRx : Actual value of room temperature
TRw : Room temperature setpoint
SDR : Room switching differential
P : Pump
T : Time
Building time constant [h]
Composite
outside
temperature
5
Duration of quick setback [h]
15°C
7.7
10°C
3.3
5°C
2.1
0°C
1.6
-5°C
1.3
-10°C
1.0
-15°C
0.9
-20°C
0.8
Optimisation at switch-on and switch-off
LINE
FUNCTION
HC1
HC2
790
1090
Optimum start control max
791
1091
Optimum stop control max
Optimum start control max
The change in temperature levels is optimised in
such a way as to reach the comfort setpoint during
changeover times.
Optimum stop control max
The change in temperature levels is optimised in
such a way as to reach the comfort setpoint -1/4 °C
during changeover times.
Содержание Waterstage WOYG140LCTA
Страница 21: ... OU01 16 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LF OUTDOOR UNIT WO A060 100LF MODEL WO A080LFCA ...
Страница 22: ... OU01 17 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LF OUTDOOR UNIT WO A060 100LF MODEL WO A100LFTA ...
Страница 36: ...1 OUTDOOR UNIT DTW_1SP006E_01 CHAPTER01 2018 02 18 SINGLE PHASE TYPE WO G112LCTA WO G140LCTA ...
Страница 64: ...1 OUTDOOR UNIT DTW_3SP003E_01 CHAPTER01 2016 02 18 3 PHASE TYPE WO K112LCTA WO K140LCTA WO K160LCTA ...
Страница 199: ... CS01 83 Control system CS01 83 CONTROL SYSTEM CONTROL SYSTEM ...