Cooling circuit 1 functions
z
The cooling sequence is automatically started
when the room temperature is higher than the
comfort setpoint in cooling mode (line 902). The
cooling function must be activated (line 901 = Auto)
and is triggered by the programming clock (line
907). The cooling sequence is interrupted as soon
as heating circuit 1 indicates a need for heat or in
the presence of a heat demand signal from a DHW
circuit or other heating circuit (only if cooling is
active).
The controller measures the current room
temperature and compares it with the room
temperature setpoint to compute the flow
temperature setpoint. If the temperature is not low
enough the heat pump is started to provide cooling
(reversed control of the mixing valve).
The following settings apply to the hydraulic circuit
in zone 1 (HC1). If there is a second zone, this
zone can be cooled with the setting (line 963)
which will connect the pump directly to zone 2. This
will require setting the "Mixing valve sub-cooling"
parameter (line 938) to a suitable value in order for
both zones to be adequately cooled according to
the available emitters.
Warning:
Cooling mode is prohibited on all radiators, heating
only floors, or any emitters not intended for this
purpose.
Operating Mode
LINE
FUNCTION
901
Operating mode
(Off / Automatic)
The cooling key on the user interface enables
switching between operating modes.
Off
•
The cooling function is deactivated.
Automatic
•
The cooling function is automatically activated by
the time program (line 907), the holiday program,
the occupancy key, or according to the need.
Comfort cooling setpoint
LINE
FUNCTION
902
Comfort cooling setpoint
In cooling mode the room temperature control
follows the comfort setpoint adjusted under this
setting. The cooling comfort setpoint can be
displayed with a knob on the room unit.
In summer the comfort setpoint is gradually
increased in relation to the outdoor temperature
(see lines 918-920).
Release
LINE
FUNCTION
907
Release
(24h/day / Heating circuit time pgm / Time program 5)
The "Release" setting determines the time program
according to which cooling is released.
24h/day
•
Cooling is continuously activated (24h/Day).
Time program HC
•
Cooling is activated according to the heating circuit
time program.
Time program 5
•
Cooling is released according to time program 5.
Содержание Waterstage WOYG140LCTA
Страница 21: ... OU01 16 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LF OUTDOOR UNIT WO A060 100LF MODEL WO A080LFCA ...
Страница 22: ... OU01 17 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LF OUTDOOR UNIT WO A060 100LF MODEL WO A100LFTA ...
Страница 36: ...1 OUTDOOR UNIT DTW_1SP006E_01 CHAPTER01 2018 02 18 SINGLE PHASE TYPE WO G112LCTA WO G140LCTA ...
Страница 64: ...1 OUTDOOR UNIT DTW_3SP003E_01 CHAPTER01 2016 02 18 3 PHASE TYPE WO K112LCTA WO K140LCTA WO K160LCTA ...
Страница 199: ... CS01 83 Control system CS01 83 CONTROL SYSTEM CONTROL SYSTEM ...