- (CS01 - 06) -
Control system
- (CS01 - 06) -
C
O
N
T
R
O
L
SY
S
T
E
M
C
O
N
T
R
O
L
SY
S
T
E
M
Ref 3
Functions
- Definitions
Hydraulic unit :
Flashing of the LED visible on the interface card.
LED display
Error contents
LED 2 (green)
LED 1 (red)
1 Flash
1 Flash
Communication error between Hydraulic unit and Outdoor unit.
2 Flashes
3 Flashes
Connection forbidden (series error).
3 Flashes
1 Flash
Indoor unit power supply abnormal.
3 Flashes
2 Flashes
Serial communication error between Controller /Interface PCBs.
4 Flashes
1 Flash
Heat pump capacity signal error (Open or short).
4 Flashes
2 Flashes
Hydraulic unit heat-exchange thermister error.
6 Flashes
1 Flash
Outdoor unit power supply abnormal.
6 Flashes
2 Flashes
Outdoor unit main PCB error.
6 Flashes
3 Flashes
Inverter error.
6 Flashes
4 Flashes
Active filter error.
6 Flashes
5 Flashes
Outdoor unit IPM error.
6 Flashes
7 Flashes
Outdoor unit power short interruption error (protective operation).
6 Flashes
8 Flashes
Outdoor unit magnetic relay error.
7 Flashes
1 Flash
Discharge thermister error.
7 Flashes
2 Flashes
Compressor thermister error.
7 Flashes
3 Flashes
Heat-exchange thermistor (outlet / intermediate) error.
7 Flashes
4 Flashes
Outdoor thermistor error.
7 Flashes
7 Flashes
Outdoor unit heat sink temp. thermistor error.
7 Flashes
8 Flashes
Expansion valve thermistor error.
8 Flashes
4 Flashes
Current sensor error.
8 Flashes
6 Flashes
Pressure sensor error / Pressure switch error.
9 Flashes
4 Flashes
Current trip.
9 Flashes
5 Flashes
Detection of compressor position error. / Compressor start up error.
9 Flashes
7 Flashes
Outdoor unit fan motor 1 error.
9 Flashes
8 Flashes
Outdoor unit fan motor 2 error.
10 Flashes
1 Flash
Discharge temperature protection.
10 Flashes
3 Flashes
Compressor temperature protection.
10 Flashes
4 Flashes
Outdoor unit pressure error.
10 Flashes
5 Flashes
Low pressure abnormal.
10 Flashes
9 Flashes
Current overload error.
Continuous flashing (1 sec On / 1
sec Off)
Pump down operation.
Continuous
lighting
Off
Defrosting.
-
Information concerning maintenance, special mode.
Содержание Waterstage WOYG140LCTA
Страница 21: ... OU01 16 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LF OUTDOOR UNIT WO A060 100LF MODEL WO A080LFCA ...
Страница 22: ... OU01 17 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LF OUTDOOR UNIT WO A060 100LF MODEL WO A100LFTA ...
Страница 36: ...1 OUTDOOR UNIT DTW_1SP006E_01 CHAPTER01 2018 02 18 SINGLE PHASE TYPE WO G112LCTA WO G140LCTA ...
Страница 64: ...1 OUTDOOR UNIT DTW_3SP003E_01 CHAPTER01 2016 02 18 3 PHASE TYPE WO K112LCTA WO K140LCTA WO K160LCTA ...
Страница 199: ... CS01 83 Control system CS01 83 CONTROL SYSTEM CONTROL SYSTEM ...