SAFETY DEVICES
91
Protection from
Model
WO
A060LFCA
WO
A080LFCA
WO
A100LFTA
Circuit protection
Current fuse
(Near the terminal)
250V 20A
250V 25A
250V 25A
Current fuse
(Main PCB)
250V 15A
250V 3.15A
250V 3.15A
250V 10A
250V 3.15A
Fan motor protection
Thermal protection
program
Activate (at 100 ± 10 °C): Fan motor stop
Reset (at 95 ± 10 °C): Fan motor restart
Activate (at 150 ± 15 °C):
Fan motor stop
Reset (at 120 ± 15 °C):
Fan motor restart
Compressor protection
Thermal protection program
(Compressor temp.)
Activate (at 108 °C): Compressor stop
Reset (at 80 °C): Compressor restart
Thermal protection program
(Discharge temp.)
Activate (at 110 °C): Compressor stop
Reset (after 7 minutes): Compressor restart
High pressure protection
Thermal protection program
(Heat exchanger temp.)
Activate (at 67 °C): Compressor stop
Reset (at 63 °C): Compressor restart
Pressure sensor
Activate (at 4.2 MPa): Compressor stop
Reset (at 3.0 MPa): Compressor restart
Low pressure protection
(Cooling mode only)
Pressure sensor
Activate (at 0.12 MPa): Compressor stop
Reset (at 0.15 MPa): Compressor restart
Содержание Waterstage WOYG140LCTA
Страница 21: ... OU01 16 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LF OUTDOOR UNIT WO A060 100LF MODEL WO A080LFCA ...
Страница 22: ... OU01 17 Outdoor unit Single phase OUTDOOR UNIT WO A060 100LF OUTDOOR UNIT WO A060 100LF MODEL WO A100LFTA ...
Страница 36: ...1 OUTDOOR UNIT DTW_1SP006E_01 CHAPTER01 2018 02 18 SINGLE PHASE TYPE WO G112LCTA WO G140LCTA ...
Страница 64: ...1 OUTDOOR UNIT DTW_3SP003E_01 CHAPTER01 2016 02 18 3 PHASE TYPE WO K112LCTA WO K140LCTA WO K160LCTA ...
Страница 199: ... CS01 83 Control system CS01 83 CONTROL SYSTEM CONTROL SYSTEM ...