Heat Pump, Split System, Single Service, 3 phase
Maintenance Document
1394-1
81
"Manual controlled curing" setpoint
The flow temperature setpoint for the "Manual"
controlled floor drying function can be adjusted
separately for each heating circuit.
Current controlled curing setpoint
Displays the current flow temperature setpoint for the
controlled floor drying function
Current day of controlled curing
Displays the current day of the controlled floor drying
function
Important:
After a power outage, the installation resumes the
controlled drying function as it was when the outage
occurred.
Operating Mode Changeover
Line no.
HC1
HC2
Programming line
900 1200
Optg
mode
changeover
(None / Frost protection mode / Reduced / Comfort / Automatic)
In case of an external changeover via input H2 (on
the extension module only) the operating mode to
which the changeover will be performed must be
previously defined.
Heating Circuit Frost Protection
The heating circuit frost protection is continuously
activated (protection mode
) and is not adjustable.
Heating circuit frost protection in heating mode
If the flow temperature is below 5°C, the controller
initiates the production of heat and starts the heating
pumps, regardless of the current heating mode.
If the flow temperature rises again above 7°C, the
controller waits another 5 minutes, and then stops the
production of heat and the heating pumps.
Heating circuit frost protection in cooling mode
See Cooling mode
Days
Heat pump
flow temp
Fh
Bh
X : Starting day
Fh + Bh