Heat Pump, Split System, Single Service, 3 phase
Maintenance Document
1394-1
33
Clear 10: Heat Sink Thermistor (inverter) error
Hydraulic Unit LED: Green 7 flashes / Red 7 flashes
Outdoor Unit LED: 9 flashes
Probable causes:
•
Misconnection.
•
Sensor
failure.
•
Inverter
PCB
failure.
Check:
1. Check the sensor connection :
-
See if the connector has been disconnected.
-
See if the connection is correct.
-
Check for any damage on the sensor cable.
After solving the misconnection problem, switch the heat pump back on.
2. Remove the sensor and check its resistance value :
- Check the resistance value.
Temperature
(°C) 0 5 10 15 20 30 40 50
Resistance (k
Ω
) 15,8 12,2
9,5 7,5 5,9
3,78 2,50 1,69
Temperature (°C)
60
70
80
90 100 120
Resistance (k
Ω
) 1,17 0,83
0,6 0,44 0,33 0,19
- If the thermistor is faulty, replace it.
OK
3. Check the electronic board voltage:
- Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
- If there is no voltage, replace Inverter PCB.
OK