Heat Pump, Split System, Single Service, 3 phase
Maintenance Document
1394-1
73
6.3.3 Time Program Functions (heating circuit 1 & 2, DHW, cooling)
Several control programs are available for the heating
circuits and the production of DHW. They are initiated
in "Automatic" mode and control the change in
temperature levels (and therefore the associated
setpoints, reduced and comfort) via the adjusted
changeover times.
Enter changeover times:
Changeover times can be adjusted in a combined
way, i.e., identical times for several days or distinct
times for certain days. Preselecting groups of days
(e.g., Mon...Fri and Sat...Sun) having the same
changeover times makes adjustment of the
changeover program considerably shorter.
Changeover Points
Line no.
HC1
HC2
4/DHW
5
Programming line
500 520 560 600 Preselection
(Mon-Sun / Mon-Fri / Sat – Sun / Mon...Sun)
501
521
561
601
1
st
phase On
502 522 562 602 1
st
phase Off
503
523
563
603
2
nd
phase On
504 524 564 604 2
nd
phase Off
505
525
565
605
3
rd
phase On
506 526 566 606 3
rd
phase Off
Standard Program
Line no.
Programming line
516, 536, 576, 616
Default values
(No /Yes)
All time programs can be reset to factory settings.
Each time program has its own command line for this
reset action.
In this case, individual settings will be lost!