
Heat Pump, Split System, Single Service, 3 phase
64
Maintenance
Document
1394-1
COMMAND
LINE
ACCESS
LEVEL
FUNCTION
SETTING RANGE
FACTORY
SETTING
523
U
2
nd
phase on
00:00…--:--
--:--
524 U
2
nd
phase off
00:00…--:--
--:--
525
U
3
rd
phase on
00:00…--:--
--:--
526 U
3
rd
phase off
00:00…--:--
--:--
536
U
Default values
No/yes
No
Time program 4 / DHW
560
U
Preselection
Mon-Sun ¦ Mon-Fri ¦ Sat - Sun ¦
Mon ¦ Tue ¦ Wed ¦Thu ¦ Fri ¦ Sat
¦Sun
Mon-Sun
561 U 1
st
phase on
00:00…--:--
00:00
562
U
1
st
phase off
00:00…--:--
05:00
563 U 2
nd
phase on
00:00…--:--
--:--
564
U
2
nd
phase off
00:00…--:--
--:--
565 U 3
rd
phase on
00:00…--:--
--:--
566
U
3
rd
phase off
00:00…--:--
--:--
576 U Default
values
No/yes
No
Time program 5 / Cooling circuit
600 U Preselection
Mon-Sun ¦ Mon-Fri ¦ Sat - Sun ¦
Mon ¦ Tue ¦ Wed ¦Thu ¦ Fri ¦ Sat
¦Sun
Mon-Sun
601
U
1
st
phase on
00:00…--:--
8:00
602 U 1
st
phase off
00:00…--:--
20:00
603
U
2
nd
phase on
00:00…--:--
--:--
604 U 2
nd
phase off
00:00…--:--
--:--
605
U
3
rd
phase on
00:00…--:--
--:--
606 U 3
rd
phase off
00:00…--:--
--:--
616
U
Default values
No/yes
No
Holidays heating circuit 1
641
U
Preselection
Period 1…8
Period 1
642 U
Start 01.01…31.12
643
U
End
01.01…31.12
648 U
Operating level
Frost protection ¦ Reduced
Frost protection
Holidays heating circuit 2
651
U
Preselection
Period 1…8
Period 1
652 U
Start 01.01…31.12
653
U
End
01.01…31.12
658 U
Operating level
Frost protection ¦ Reduced
Frost protection
Heating circuit 1
710 U
Comfort heating setpoint
Reduced temp to
35°C
20°C
712
U
Reduced setpoint
18°C
714 U
Frost protection setpoint
4°C to Reduced
temp
8°C
716
S
Comfort setpoint max
20°C…35°C
28°C
720
I
Heating curve slope
0,1…4
0,5
721
I
Heating curve displacement
-4,5°C…4,5°C
0°C
726 I Heating
curve
adaptation Off,
on Off
730
I
Summer/winter heating limit
8°C…30°C
18°C
732
S
24-Hour heating limit
-10°C…10°C
-3°C
740
S
Flow temp setpoint min (for fan
convectors)
8°C… 95°C
8°C
741
S
Flow temp setpoint max
8°C… 95°C
55°C
Floor heating system = 50 °C / Higher temperature radiator = 65 °C
750
S
Room influence
1%...100%
20%
790
S
Optimum start control max
0…360min
120 min
791
S
Optimum stop control max
0…360min
120 min
800
S
Reduced setpoint increase start
-30°C…10°C
---
801
S
Reduced setpoint increase end
-30°C…10°C
-5°C
830
S
Mixing valve boost
0…50°C
0