Heat Pump, Split System, Single Service, 3 phase
Maintenance Document
1394-1
25
4.1.2 Outdoor Unit Fault
When the system is switched back on after a power
outage, the Hydraulic Unit may display fault 370 for a
few tens of seconds. This is not a serious problem. It
simply means that the outdoor unit is running its
tests. Once the tests have been completed, the fault
should disappear.
If it doesn't, if a fault has occurred on the outdoor unit
as indicated by the Hydraulic Unit, you must remove
the front (right-hand) facing from the outdoor unit.
Faults are coded by LED flashes. Error messages are
listed in the table below:
On the outdoor unit
When an error occurs:
-
The diode “
ERROR
” (2) blinks
Press once on the switch “
ENTER
” (SW4)
- The
“
ERROR
” (2) diode blinks several times depending on the error’s type
Location of switches and diodes on outdoor unit
LED display on the outdoor unit
LED display
Hydraulic Unit
Diagnosis
Clear
Green
Red
Outdoor unit
Off
Serial reverse transfer error.
1
1 flash
1 flash
1 flash
Serial forward transfer error.
2
4 flashes
1 flash
22 flashes
Heat pump capacity signal error
4
4 flashes
2 flashes 22 flashes
Hydraulic Unit Heat ex. Sensor error
5
6 flashes
3 flashes 18 flashes
Inverter error.
20
6 flashes
4 flashes 19 flashes
P.F.C. error.
27
7 flashes
1 flash
2 flashes
Discharge thermistor error.
7
7 flashes
2 flashes 8 flashes
Compressor thermistor error.
11
5 flashes
Heat-exchange thermistor (intermediate) error.
12
7 flashes
3 flashes
4 flashes
Heat-exchange thermistor (outlet) error.
8
7 flashes
4 flashes 7 flashes
Outdoor temperature thermistor error.
9
9 flashes
Heat sink thermistor (inverter) error.
10
7 flashes
7 flashes
10 flashes
Heat sink thermistor (P.F.C.) error.
13
7 flashes
8 flashes 6 flashes
Expansion valve thermistor error.
14
8 flashes
6 flashes 3 flashes
Pressure sensor error.
24
9 flashes
4 flashes 13 flashes
Current trip (permanent stoppage).
15
14 flashes
Detection of compressor position error (permanent stoppage).
33
9 flashes
5 flashes
15 flashes
Compressor start up error (permanent stoppage).
17
16 flashes
Outdoor unit fan 1 motor error.
9 flashes
7 flashes
17 flashes
Outdoor unit fan 2 motor error.
18
10 flashes 1 flash
11 flashes
Discharge temperature protection (permanent stoppage).
22
10 flashes 3 flashes 12 flashes
Compressor temperature protection (permanent stoppage).
25
10 flashes 5 flashes 20 flashes
Low pressure abnormal.
26