![Fujitsu WATERSTAGE 112 Скачать руководство пользователя страница 8](http://html.mh-extra.com/html/fujitsu/waterstage-112/waterstage-112_maintenance-document_118748008.webp)
Heat Pump, Split System, Single Service, 3 phase
8
Maintenance
Document
1394-1
1.2.5 Performance Curves for Waterstage 160
1.3 Hydraulic
Characteristics
HEAT PUMP
WATERSTAGE
112
WATERSTAGE
140
WATERSTAGE
160
Connection diameter
1’’ – 25.4 mm (male)
Exchanger tank volume (L)
25
Expansion vessel volume (L)
8
Max pressure water circuit (Bar)
3
Max flow rate (l/h)
2400
3000
3400
Min flow rate (l/h)
1200
1500
1700
Min Delta T (°C)
4
Max Delta T (°C)
8