Heat Pump, Split System, Single Service, 3 phase
66
Maintenance
Document
1394-1
COMMAND
LINE
ACCESS
LEVEL
FUNCTION
SETTING RANGE
FACTORY
SETTING
1156 I
Floor curing day current
0…32
1157
I
Floor curing days completed
0…32
1200 S Optg
mode
changeover
Protection mode
Domestic hot water
1610 U Nominal
setpoint
Thc…65°C 50°C
1612
U
Reduced setpoint
8°C….Thc
25°C
1620 I Release
24h/day
Heating circ time pgms
Time program 4/DHW
Off-peak rate
4: Time pgm 4/DHW or
Off-peak rate
Time program
4/DHW
1640
I
Legionella function
Off
Periodic
Fixed day in week
Off
1641
I
Legionella funct periodically
1 to 7
7
1642
I
Legionella funct weekday
Mon,…Sun
Saturday
1644
I
Legionella funct time
00:00…23:50
--:--
1645
I
Legionella funct setpoint
55°C…95°C
65°C
1646
I
Legionella funct duration
10min…360min
30
1647
I
Legionella funct circ pump
On/off
On
1660
I
Circulation pump release
Time program 3/HCP
DHW release
Time program 4/DHW
DHW release
Swimming pool
2056
U
Setpoint source heating
8…80
22
Heat pump
2844
S
Switch-off temp max
8°C… 100°C
55°C
Floor heating system = 55 °C / Higher temperature radiator = 65 °C
2882
S
Release integr electric flow
0… 500°Cmin
100°Cmin
2884
S
Release el flow at OT
-30°C…30°C
2°C
2910
S
Release above OT
---/-30°C…30°C
---
2920
S
With electrical utility dock
Lock/release
Released
Supplementary source
3700
S
Release below outside temp
-50…50°C
2°C
3705
S
Overrun time
0...120min
20
3720
S
Switching integral
0… 500°Cmin
100°Cmin
DHW storage tank
5020
S
Flow setpoint boost
0…30°C
5°C
5024
S
Switching differential
0…20°C
7°C
5030
S
Charging time limitation
10…600min
90 min
5060
S
El imm heater optg mode
Substitution
Summer
Always
Cooling mode
Substitution
5061
S
Electric immersion heater release
24h/day
DHW release
Time program 4/DHW
DHW release
Configuration
5700
I
Preselection
1 to 12
1
5711
S
Cooling circuit 1
Off
4-pipe system
2-pipe system
Off
5870 S Combi
storage
tank
No/yes
No
5987
S
Cont type input EX4
Normally-closed contact
(NC)
Normally-opened contact
(NO)
NO
5989
S
Cont type input EX5
Normally-closed contact
(NC)
Normally-opened contact
(NO)
NC