15) Primary and secondary settings
Set the indoor unit that is connected to the outdoor unit using a transmission cable as the primary.
Function number
Setting value
Setting description
Factory setting
51
00
Primary
♦
01
Secondary
16) Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External input and
output”.
Function number
Setting value
Setting description
Factory setting
60
00
Operation status
♦
01—08
(Setting prohibited)
09
Error status
10
Fresh air control
10
Indoor unit fan operation status
11
External heater
1-8. Function details
- (05-32) -
1. Function settings
FIELD
WORKING
FIELD
WORKING