3. Fan control
Tr: Room temperature
Ts: Setting temperature
3-1. Indoor fan control
¢
Compact cassette type
Fan speed
Indoor fan speed is defined as below.
Operation mode
Fan mode
Speed (rpm)
AUXG18KVLA
AUXG22KVLA
AUXG24KVLA
Heating
HIGH
830
880
960
MED+
770
850
930
MED
730
800
880
LOW
630
740
740
QUIET
500
580
580
Cool air prevention
400
400
400
S-LOW
300
300
300
Cooling/Fan
HIGH
730
860
960
MED
630
770
850
LOW
540
650
650
QUIET
460
500
500
Soft quiet
400*
1
400*
1
400*
1
S-LOW
300*
2
300*
2
300*
2
Dry
X zone: 460
J zone: 460
X zone: 500
J zone: 500
X zone: 500
J zone: 500
*1: Fan mode only
*2: Cooling mode only
Fan operation
Airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH while indoor unit fan
only runs.
When fan mode is set at AUTO, it operates on MED fan speed.
Cooling operation
Switch the airflow AUTO, and indoor fan motor will run according to room temperature, as below.
On the other hand, if switched in HIGH—QUIET, indoor motor will run at a constant airflow of COOL
operation modes QUIET, LOW, MED, HIGH as shown in “Fan speed” above.
Airflow change over (Cooling: Auto)
When room
temperature rises
When room
temperature drops
Tr - Ts ≥ 2
°C
HIGH mode
MED mode
LOW mode
2
°C
> Tr - Ts ≥ 1
°C
1
°C > Tr - Ts
Tr - Ts ≥ 2.5
°C
2.5
°C
> Tr - Ts ≥ 1.5
°C
1.5
°C > Tr - Ts
3-1. Indoor fan control
- (04-12) -
3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AUXG18KVLA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 05 19 SR_CH01_SM001EG_02 ...
Страница 22: ...3 4 Outdoor unit 01 16 3 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 23: ...2 TECHNICAL DATA AND PARTS LIST 2021 06 15 SR_CH02_SM001EG_04 ...
Страница 69: ...3 TROUBLESHOOTING 2021 06 15 SR_CH03_SM001EG_03 ...
Страница 72: ......
Страница 143: ...4 CONTROL AND FUNCTIONS 2021 05 19 SR_CH04_SM001EG_02 ...
Страница 146: ......
Страница 185: ...5 FILED WORKING 2021 06 15 SR_CH05_SM001EG_03 ...