2-30. E: 95. Compressor motor control error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 95
Detective actuator
Outdoor unit
Main PCB
"Protection stop by "overcurrent generation at inverter
compressor starting" restart" generated consecutively 10
times x 3 sets (total 30 times)
Compressor
Forecast of cause
Defective connection of electric components
Main PCB failure
Compressor failure
Check point 1. Check noise from compressor
Turn on power and check operation noise.
→ If an abnormal noise show, replace compres-
sor.
↓
Check point 2. Check connection of around the compressor components
For compressor terminal, main PCB
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open. (Refer to inverter compressor in
→ Upon correcting the removed connector or mis-wiring, reset the power.
↓
Check point 3. Replace main PCB
If Check point 1, 2 do not improve the symptom, change main PCB.
↓
Check point 4. Replace compressor
If Check point 3 do not improve the symptom, change compressor.
↓
End
2-30. E: 95. Compressor motor control error (Outdoor unit)
- (03-37) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание AUXG18KVLA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 05 19 SR_CH01_SM001EG_02 ...
Страница 22: ...3 4 Outdoor unit 01 16 3 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 23: ...2 TECHNICAL DATA AND PARTS LIST 2021 06 15 SR_CH02_SM001EG_04 ...
Страница 69: ...3 TROUBLESHOOTING 2021 06 15 SR_CH03_SM001EG_03 ...
Страница 72: ......
Страница 143: ...4 CONTROL AND FUNCTIONS 2021 05 19 SR_CH04_SM001EG_02 ...
Страница 146: ......
Страница 185: ...5 FILED WORKING 2021 06 15 SR_CH05_SM001EG_03 ...