8-3. Current release control
The compressor frequency is controlled so that the outdoor unit input current does not exceeds cur-
rent limit value set according to the outdoor temperature.
The compressor frequency returns according to the operation mode, when the current becomes low-
er than the release value.
¢
Model: AOHG36KRTA
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
52°C ≤ Ta
3.5 A
3.0 A
50°C ≤ Ta < 52°C
5.5 A
5.0 A
42°C ≤ Ta < 50°C
6.0 A
5.5 A
2°C ≤ Ta < 42°C
7.5 A
7.0 A
Ta < 2°C
8.5 A
8.0 A
Heating
20°C ≤ Ta
5.5 A
5.0 A
16°C ≤ Ta < 20°C
6.0 A
5.5 A
12°C ≤ Ta < 16°C
7.0 A
6.5 A
2°C ≤ Ta < 12°C
7.5 A
7.0 A
Ta < 2°C
8.5 A
8.0 A
¢
Models: AOHG45KRTA and AOHG54KRTA
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
52°C ≤ Ta
4.5 A
4.0 A
50°C ≤ Ta < 52°C
5.5 A
5.0 A
46°C ≤ Ta < 50°C
6.5 A
6.0 A
42°C ≤ Ta < 46°C
7.5 A
7.0 A
2°C ≤ Ta < 42°C
8.5 A
8.0 A
Ta < 2°C
10.0 A
9.5 A
Heating
20°C ≤ Ta
6.5 A
6.0 A
16°C ≤ Ta < 20°C
7.0 A
6.5 A
12°C ≤ Ta < 16°C
8.0 A
7.5 A
2°C ≤ Ta < 12°C
8.5 A
8.0 A
Ta < 2°C
10.0 A
9.5 A
8-3. Current release control
- (04-35) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AUXG18KVLA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 05 19 SR_CH01_SM001EG_02 ...
Страница 22: ...3 4 Outdoor unit 01 16 3 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 23: ...2 TECHNICAL DATA AND PARTS LIST 2021 06 15 SR_CH02_SM001EG_04 ...
Страница 69: ...3 TROUBLESHOOTING 2021 06 15 SR_CH03_SM001EG_03 ...
Страница 72: ......
Страница 143: ...4 CONTROL AND FUNCTIONS 2021 05 19 SR_CH04_SM001EG_02 ...
Страница 146: ......
Страница 185: ...5 FILED WORKING 2021 06 15 SR_CH05_SM001EG_03 ...