8-5. Indoor unit fan motor over temperature protection
¢
Compact cassette type
When satisfy the following conditions, the protection works.
• After the 90 seconds from the fan operation, detect less than 300 rpm for 10 seconds.
• IPM trip protection works.
• Current overload protection works.
When detecting the above condtion, recheck the condition after 6 minutes. When count the twice,
the protection works.
•
Protection contents
Reduce the static pressure 20 Pa. When it does not dissolve even the minimum static pressure
condition, work the following operation.
– Fan motor error displayed when less than 300 rpm for 10 seconds is detected after the 90 sec-
onds from the fan operation.
– Fan stop 40 seconds when IPM trip protection works.
– Fan stop 50 seconds when corrent overload protection works.
¢
Slim duct and Medium static pressure duct types
When satisfy the following conditions, the protection works.
• After the 90 seconds from the fan operation, detect less than 200 rpm for 10 seconds.
• IPM trip protection works.
• Current overload protection works.
When detecting the above condtion, recheck the condition after 6 minutes. When count the twice,
the protection works.
•
Protection contents
Reduce the static pressure 20 Pa. When it does not dissolve even the minimum static pressure
condition, work the following operation.
– Fan motor error displayed when less than 200 rpm for 10 seconds is detected after the 90 sec-
onds from the fan operation.
– Fan stop 40 seconds when IPM trip protection works.
– Fan stop 50 seconds when corrent overload protection works.
8-6. Compressor temperature protection
When the compressor temperature sensor detects higher than the trigger condition below, the com-
pressor is stopped. When the compressor temperature sensor detects the release condition, the pro-
tection is released.
Trigger condition
108°C
Release condition
80°C
(3 minutes after compressor stop)
8-5. Indoor unit fan motor over temperature protection
- (04-37) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AUXG18KVLA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 05 19 SR_CH01_SM001EG_02 ...
Страница 22: ...3 4 Outdoor unit 01 16 3 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 23: ...2 TECHNICAL DATA AND PARTS LIST 2021 06 15 SR_CH02_SM001EG_04 ...
Страница 69: ...3 TROUBLESHOOTING 2021 06 15 SR_CH03_SM001EG_03 ...
Страница 72: ......
Страница 143: ...4 CONTROL AND FUNCTIONS 2021 05 19 SR_CH04_SM001EG_02 ...
Страница 146: ......
Страница 185: ...5 FILED WORKING 2021 06 15 SR_CH05_SM001EG_03 ...