7-8. Drain pump control
¢
Drain control for dehumidification operation
During cooling or dry mode
• On the main unit, when the compressor starts, the drain pump unit starts simultaneously.
When the sub unit receives the signal from the main unit, the drain pump of the sub unit starts
simultaneously.
• On the main unit, the drain pump operates continuously for 3 minutes after the compressor is
turned off.
When the sub unit receives the signal from the main unit, the drain pump of the sub unit oper-
ates continuously for 3 minutes after the compressor is turned off.
3 minutes
On
Off
On
Off
Compressor
Drain pump
• When the compressor stops by the
"Anti-freezing control (cooling and dry mode)"
34, the drain pump is turned off in 1 hour after the compressor stops.
• When the float switch is on, the compressor, indoor and outdoor fan motor operation are
stopped. The sub unit sends the signal to the main unit simultaneously.
• When the float switch is turned off, the sub unit sends the signal to the main unit. Drain pump
operates continuously for 3 minutes after the float switch is turned off and then drain pump is
turned off.
• When the float switch turns on continuously for 3 minutes, "failure indication" operates. (It is
necessary to turn off power for release it.)
• When the float switch turns off less than 3 minutes, the unit starts cooling operation. Indoor
fan motor starts after the float switch is turned off and the compressor starts after 3 minutes st.
3 minutes
3 minutes ST
On
Off
On
Off
On
Off
On
Off
Float switch
Compressor
Indoor fan
Drain pump
Less than 3 minutes
7-8. Drain pump control
- (04-31) -
7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AUXG18KVLA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 05 19 SR_CH01_SM001EG_02 ...
Страница 22: ...3 4 Outdoor unit 01 16 3 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 23: ...2 TECHNICAL DATA AND PARTS LIST 2021 06 15 SR_CH02_SM001EG_04 ...
Страница 69: ...3 TROUBLESHOOTING 2021 06 15 SR_CH03_SM001EG_03 ...
Страница 72: ......
Страница 143: ...4 CONTROL AND FUNCTIONS 2021 05 19 SR_CH04_SM001EG_02 ...
Страница 146: ......
Страница 185: ...5 FILED WORKING 2021 06 15 SR_CH05_SM001EG_03 ...