3-3. No operation (Power is on)
Forecast of cause
Setting/ Connection failure
External cause
Electrical components defective
Check point 1. Check indoor and outdoor installation condition
•
Indoor unit:
–
Check incorrect wiring between indoor unit and remote controller.
–
Check if there is an open cable connection.
•
Are these indoor unit, outdoor unit, and remote controller suitable model numbers to connect?
-> If there is some abnormal condition, correct it by referring to the installation manual and “DESIGN
& TECHNICAL MANUAL”.
↓
Turn off the power and check correct followings.
•
Is there loose or removed communication line of indoor unit and outdoor unit?
↓
Check point 2. Check external cause at indoor and outdoor (Voltage drop or Noise)
•
Instant drop: Check if there is a large load electric apparatus in the same circuit.
•
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
•
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
↓
Check point 3. Check wired remote controller and controller PCB
[AU type]
Check voltage at CN14 of controller PCB. (Terminal 1—3, Terminal 1—2).
(Power supply to remote controller)
•
If it is DC 12 V, remote controller is failure. (The controller PCB is normal)
-> Replace remote controller.
•
If it is DC 0 V, controller PCB is failure. (Check the remote controller once
again)
-> Replace controller PCB.
[AR type]
Check voltage at CN300 of controller PCB. (Terminal 1—3, Terminal 1—2).
(Power supply to remote controller)
•
If it is DC 13 V, remote controller is failure. (The controller PCB is normal)
-> Replace remote controller.
•
If it is DC 0 V, controller PCB is failure. (Check the remote controller once
again)
-> Replace controller PCB.
↓
3-3. No operation (Power is on)
- (03-51) -
3. Troubleshooting without error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание AUXG18KVLA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 05 19 SR_CH01_SM001EG_02 ...
Страница 22: ...3 4 Outdoor unit 01 16 3 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 23: ...2 TECHNICAL DATA AND PARTS LIST 2021 06 15 SR_CH02_SM001EG_04 ...
Страница 69: ...3 TROUBLESHOOTING 2021 06 15 SR_CH03_SM001EG_03 ...
Страница 72: ......
Страница 143: ...4 CONTROL AND FUNCTIONS 2021 05 19 SR_CH04_SM001EG_02 ...
Страница 146: ......
Страница 185: ...5 FILED WORKING 2021 06 15 SR_CH05_SM001EG_03 ...