En-3

 CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may 

cause water leaks.

Use heat insulation with heat resistance above 248 °F (120 °C). Reverse cycle model 

only.

In addition, if the humidity level at the installation location of the refrigerant piping 

is expected to exceed 70%, install heat insulation around the refrigerant piping. If 

the expected humidity level is 70-80%, use heat insulation that is 3/4 in. (15 mm) or 

thicker and if the expected humidity exceeds 80%, use heat insulation that is 13/16 in. 

(20 mm) or thicker.

If heat insulation is used that is not as thick as specified, condensation may form on 

the surface of the insulation. In addition, use heat insulation with heat conductivity of 

0.045 W/(m•K) or less (at [68 °F (20 °C)]).

3.2. Electrical requirement

The indoor unit is powered from the outdoor unit or branch box. Do not power indoor unit 
from separate power source.

 WARNING

 Refer to local codes for acceptable cable type.

4.  SELECTING THE INSTALLATION LOCATION

Decide the mounting position with the customer as follows:
(1)  Install the indoor unit level on a strong wall which is not subject to vibration.

(2)  The inlet and outlet ports should not be obstructed: the air should be able to blow all 

over the room.

(3)  Install the unit a dedicated electrical branch circuit.

(4)  Do not install the unit where it will be exposed to direct sunlight.

(5)  Install the unit where connection to the outdoor unit or branch box is easy.

(6)  Install the unit where the drain pipe can be easily installed.

(7)  Take servicing, etc. into consideration and leave the spaces shown in [5.1. Installation 

dimensions]. Also install the unit where the filter can be removed.

Correct initial installation location is important because it is difficult to move unit after it is 

installed.

 WARNING

 Install the air conditioner in a location which can withstand a load of at least 3 times the 

weight of the main unit and which will not amplify sound or vibration. If the installation 

location is not strong enough, the indoor unit may fall and cause injuries.

Withstandable weight (Unit weight x 3*)

120 Lbs (54kg)

*In accordance with UL standards.

 CAUTION

Do not install the unit in the following areas:

• Area with high salt content, such as at the seaside. It will deteriorate metal parts, caus-

ing the parts to fail or the unit to leak water.

•  Area filled with mineral oil or containing a large amount of splashed oil or steam, such 

as a kitchen. 

It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.

•  Area that generates substances that adversely affect the equipment, such as sulfuric 

gas, chlorine gas, acid, or alkali. 

It will cause the copper pipes and brazed joints to corrode, which can cause refrigerant 

leakage.

•  Area that can cause combustible gas to leak, contains suspended carbon fibers or 

flammable dust, or volatile inflammables such as paint thinner or gasoline.

• If gas leaks and settles around the unit, it can cause a fire.

•  Area where animals may urinate on the unit or ammonia may be generated.

•  Do not use the unit for special purposes, such as storing food, raising animals, grow-

ing plants, or preserving precision devices or art objects.

It can degrade the quality of the preserved or stored objects.

•  Do not install where there is the warning of combustible gas leakage.

•  Do not install the unit near a source of heat, steam, or flammable gas.

•  Install the unit where drainage does not cause any trouble.

•  Install  the  indoor  unit,  outdoor  unit,  branch  box,  power  supply  cable,  transmission 

cable, and remote controller cable at least 40 in. (1m) away from a television or radio 

receivers. The purpose of this is to prevent TV reception interference or radio noise. 

(Even if they are installed more than 40 in. (1m) apart, you could still receive noise 

under some signal conditions.)

•  If children under 10 years old may approach the unit, take preventive measures so 

that they cannot reach the unit.

•  Install the indoor unit on the wall where the height from the floors more than 70 in.  

(1.8 m).

5.  INSTALLATION WORK

 CAUTION

•  Do not hit or push the human sensor. This may lead to damage or malfunction.

•  Do not touch the human sensor. Any scratches or dirt may lead to incorrect detection.

•  Do not place large objects near the human sensor. Also keep heating units outside 

the sensor’s detection area.

90°

50°

50°

Detection range of the human sensor is as follows.

22ft (7m)

22ft

 (7m)

Vertical angle 90° (Side view)

Horizontal angle 100° (Top view)

5.1. Installation dimensions

(Wall cap)

59 (1.5 m) 

or over

2-3/8 (60) or over**

3 (80) or over*

Wall hook bracket

5-1/8 (130) or 

over**

70 (1.8 m) or over

*  The distance between the wall hook 

bracket and the ceiling should be  

3 in (80 mm) or more.

** The side next to the sidewall must 

follow the size indicated in figure.

Remote 

controller

Remote  

controller  

holder

Tapping screw 

(small)

Unit: in. (mm)

5.2. Indoor unit piping direction

The piping can be connected in the 6 directions indicated in the following.

When the piping is connected to direction (B) , (C) , (D) or (E) , cut along the piping groove 

on the side of the front cover with a hacksaw.

 

 

 

 

 

 

 

(B)  Right 

outlet

(A)  Rear 

outlet

(C)  Bottom 

outlet

(D)  Left bottom 

outlet

(E)  Left 

outlet

(Rear)

(F)  Centre 

outlet

(G)  Left rear 

outlet

5.3. Cutting the hole in the wall for the connecting piping

(1)  Cut a 80 mm diameter hole in the wall at the position shown in the following.

(2)  Cut the hole so that the outside end is lower (5 to 10 mm) than the inside end.

(3)  Always align the center of the wall hole. If misaligned, water leakage will occur.

(4)  Cut the wall pipe to match the wall thickness, stick it into the wall cap, fasten the cap with 

vinyl tape, and stick the pipe through the hole.

(5)  For left piping and right piping, cut the hole a little lower so that drain water will flow 

freely. 

Wall hook bracket

Centring marks

Lower

Lower

10 mm 

or more

80 mm hole

10 mm 

or more

80 mm hole

Wall

Fasten with 

vinyl tape

Wall cap*

Wall pipe*

(Inside)

(Outside)

5 to 10 mm low

*Locally purchased

 WARNING

Always use the wall pipe. If the wall pipe is not used, the cable that is connected between 

the indoor unit and the outdoor unit may touch metal, and cause an electric discharge.

9387082098-02_IM.indb   3

21/03/2016   10:12:50

Содержание ASU30RLE

Страница 1: ... a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water damage to walls and floors In an Area with High Winds Securely anchor the outdoor unit down with bolts and a met...

Страница 2: ... erroneous charging with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread diameter for R410A is 1 2 20 UNF Be more careful that foreign matter oil water etc does not enter the piping than with refrigerant R22 models Also when storing the piping securely seal the opening by pinching taping etc When charging the refrigerant take into account the slight ...

Страница 3: ...nimals may urinate on the unit or ammonia may be generated Do not use the unit for special purposes such as storing food raising animals grow ing plants or preserving precision devices or art objects It can degrade the quality of the preserved or stored objects Do not install where there is the warning of combustible gas leakage Do not install the unit near a source of heat steam or flammable gas ...

Страница 4: ...ck Drain cap Removal method of drain hose Remove the screw at the left of drain hose and pull out drain hose Installation method of drain hose Vertically insert the drain hose toward the inside so that the drain fixture white can ac curately align with the screw hole around the drain cock After inserting and before replacing please reinstall and fix the removed screws Please hold around the joint ...

Страница 5: ...CAUTION Connect the piping so that the control box cover can easily be removed for servicing when necessary In order to prevent water from leaking into the control box make sure that the piping is well insulated When the flare nut is tightened properly by your hand hold the body side coupling with a wrench then tighten with a torque wrench See the table below for the flare nut tightening torques T...

Страница 6: ...e terminal screw tightening torques Tightening torque lbf in N m M4 screw 11 to 16 1 2 to 1 8 CAUTION Attach the cable clamp firmly by holding the connection cable and make sure that the clamp is fixed securely Incomplete attachment of the cable clamp might cause a malfunction of the open panel Match the terminal block numbers and connection cable colors with those of the outdoor unit Erroneous wi...

Страница 7: ...ation Vinyl tape Wrap with cloth tape Cloth tape Drain hose Connection cable Pipe Drain hose Drain hose Connection pipe Wall pipe Connection cable Left piping For connection from the left rear Pipe Connection pipe heat insulation Indoor unit pipe heat insulation Bind the pipes together so that there is no gap Seal A is used when the diam eter of gas pipe is Ø12 70 or more Butt connection pipe heat...

Страница 8: ...tricted When function setting is Operation Stop mode 2 Input signal Command OFF ON Operation ON OFF Stop R C disabled 10 1 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25 m 82 ft Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed Output voltage Hi DC12V 2V Lo 0V Permissible current 5...

Страница 9: ...re to insulate the connecting parts when extending the cable Server room control For server room control connect the communication cable to the terminal block following the same procedure as the remote controller cable For details refer to the service instruction for Server room control Note Wire colors may not match Match the numbers on the terminal block of each indoor unit Tab Cable clamper and...

Страница 10: ...ch indoor unit using the Function setting a 3 wire type Function setting RC AD setting Factory setting 00 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD setting in sequence from 00 b 2 wire type Function setting RC AD setting Factory setting 00 Since the remote controller address settings are automatically configured you do not need to configur...

Страница 11: ... buttons to select the setting value Press the MIN HEAT button to switch between the left and right digits 4 Press the MODE button in the order listed to confirm the settings Please confirm that the beep sounds 5 Next please press START STOP button Please confirm that the beep sounds 6 Press the RESET button to cancel the function set ting mode 7 After completing the FUNCTION SETTING be sure to tu...

Страница 12: ...ot set first Room temperature control settings Function 30 31 92 93 will be reset and you must re do them again Heat Insulation condition building insulation Heat insulation conditions differ according to the installed environment Standard insulation 00 allows system to rapidly respond to the cooling or heating load changes High insulation 01 is when the heat insulation structure of the building i...

Страница 13: ...g to the customer in accordance with the operating manual 1 Starting and stopping method operation switching temperature adjustment timer air flow switching and other remote controller operations 2 Air filter removal and cleaning and how to use the air louvers 3 Give the operating manual to the customer 18 ERROR CODES If you use a wireless remote controller the lamp on the photo detector unit will...

Страница 14: ...sure sensor error Suction pressure sensor error High pressure switch error 9 4 Trip detection 9 5 Compressor rotor position detection error permanent stop 9 7 Outdoor unit fan motor 1 error 9 8 Outdoor unit fan motor 2 error 9 9 4 way valve error 9 10 Coil expansion valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes e...

Отзывы: