Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation
when the outdoor unit is stopped during cooling operation.
(♦... Factory setting)
Function Number
Setting
Value
Setting description
49
00
Disable
01
Enable
02
Remote controller
♦
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
02: Enable or disable this function by remote controller setting.
*When using a wired remote controller without Indoor unit fan control for energy saving for
cooling function, or when connecting a single split converter, the setting cannot be made
by using the remote controller. Set to “00” or “01”.
To confirm if the remote controller has this function, refer to the operating manual of each
remote controller.
Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External
input and output”.
(♦... Factory setting)
Function Number
Setting
Value
Setting Description
60
00
Operation status
♦
01-08
Other status
(refer to Design & Technical
manual)
09
Error status
10
Indoor unit fan operation status
Server room control switching
Switches between normal control and server room control.
To use this function, address setting of the primary unit and secondary unit needs to be done.
(♦... Factory setting)
Function Number
Setting
Value
Setting Description
96
00
Normal control
♦
01
Server room control (Primary
unit)
02
Server room control (Secondary
unit)
Setting record
Record any changes to the settings in the following table.
Setting Description
Setting Value
Filter sign
Auto restart
Room temperature sensor switching
Remote controller custom code
External input control
Room temperature sensor switching (Aux.)
Indoor unit fan control for energy saving for cooling
Switching functions for external output terminal
Server room control switching
After completing the FUNCTION SETTING, be sure to turn off the power and turn it on
again.
14.2.
Temperature correction
NOTE:
When changing Function 95, perform this setting before other Room temp. control settings
(Function 30, 31, 92, 93).
If Function 95 is not set first, Room temperature control settings (Function 30, 31, 92, 93)
will be reset and you must re-do them again.
Heat Insulation condition (building insulation)
Heat insulation conditions differ according to the installed environment.
“Standard insulation” (00) allows system to rapidly respond to the cooling or heating load
changes.
“High insulation” (01) is when the heat insulation structure of the building is high and does
not require system to rapidly respond to cooling or heating load changes.
When “High insulation” (01) is selected;
• Overheating (overcooling) is prevented at the start-up.
• All room temp. control settings (Function 30, 31, 92, 93) will reset to “No correction” [0.0°F
(0.0°C)].
(♦... Factory setting)
Function Number
Setting
Value
Setting Description
95
00
Standard insulation
♦
01
High insulation
Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may
be required.
Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the “Standard setting” (00)
(manufacturer’s recommended value).
* When Function 95-01(High insulation) is set, the “Standard setting” (00) will be the same
as “No correction” (01) [0.0°F (0.0°C)].
(♦... Factory setting)
Function Number
Setting
Value
Setting Description
30
(For cooling)
31
(For heating)
00
Standard setting*
♦
01
No correction 0.0°F (0.0°C)
02
-1°F (-0.5°C)
More
Cooling
Less
Heating
03
-2°F (-1.0°C)
04
-3°F (-1.5°C)
05
-4°F (-2.0°C)
06
-5°F (-2.5°C)
07
-6°F (-3.0°C)
08
-7°F (-3.5°C)
09
-8°F (-4.0°C)
10
+1°F (+0.5°C)
Less
Cooling
More
Heating
11
+2°F (+1.0°C)
12
+3°F (+1.5°C)
13
+4°F (+2.0°C)
14
+5°F (+2.5°C)
15
+6°F (+3.0°C)
16
+7°F (+3.5°C)
17
+8°F (+4.0°C)
Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor
may be required.
Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”.
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
(♦... Factory setting)
Function number
Setting
value
Setting description
35
(For cooling)
36
(For heating)
00
No correction 0.0°F (0.0°C)
♦
01
No correction 0.0°F (0.0°C)
02
-1°F (-0.5°C)
More
Cooling
Less
Heating
03
-2°F (-1.0°C)
04
-3°F (-1.5°C)
05
-4°F (-2.0°C)
06
-5°F (-2.5°C)
07
-6°F (-3.0°C)
08
-7°F (-3.5°C)
09
-8°F (-4.0°C)
10
+1°F (+0.5°C)
Less
Cooling
More
Heating
11
+2°F (+1.0°C)
12
+3°F (+1.5°C)
13
+4°F (+2.0°C)
14
+5°F (+2.5°C)
15
+6°F (+3.0°C)
16
+7°F (+3.5°C)
17
+8°F (+4.0°C)