5.4. Installing the wall hook bracket

(1) Install the wall hook bracket so that it is correctly positioned horizontally and vertically. 

If the wall hook bracket is titled, water will drip to the floor.

(2) Install the wall hook bracket so that it is strong enough to support the weight of the unit.

• Fasten the wall hook bracket to the wall with 5 or more screws through the holes near the 

outer edge of the bracket.

• Check that there is no rattle at the wall hook bracket.

Wall hook bracket

Tapping screw (large)

(Accessory, 8 pcs)

 CAUTION

Install the wall-hook bracket both horizontally and vertically aligned.  

Misaligned installation may cause water leakage.

5.5. Forming the drain hose and pipe

 CAUTION

•  Insert drain hose and drain cap securely. Drain should slope down to avoid water leakage.

•  When inserting, be sure not to attach any material besides water. If any other material is 

attached, it will cause deterioration and water leakage.

•  After removing drain hose, be sure not to forget mounting drain cap.

•  Be sure to fix the drain hose with tape to the bottom of piping.

•  Prevent drain water freezing under low temperature environment.

When  installing  indoor  unit’s  drain  hose  outdoors,  necessary  measure  for  frost 

protection should be taken to prevent drain water freezing.

Under low temperature environment (when outdoor temperature under 32 °F (0 °C)), 

after cooling operation is executed, water in the drain hose could be frozen. Once drain 

water is frozen, the drain hose will be blocked and water leakage may result at the 

indoor unit.

[Rear piping, Right piping, Bottom piping]

• Install the indoor unit piping in the direction of the wall hole and bind the drain hose 

and pipe together with vinyl tape.

• Install the piping so that the drain hose is at the bottom.
• Wrap the pipes of the indoor unit that are visible from the outside with decorative tape.

 

 

 

 

 

 

 

Right piping

Bind with vinyl tape

Indoor unit drain hose 

(bottom)

Pipe (top)

Rear piping

Bottom piping

[For Left rear piping, Left piping]

Interchange the drain cap and the drain hose.

Drain cap

Indoor unit 

drain hose

Remove the drain cap by pull-

ing at the projection at the end 

of the cap with pliers, etc.

For left outlet piping, cut 

off the piping outlet cutting 

groove with a hacksaw.

 

 

 

 

 

 

 

Installation method of Drain cap 

Use a hexagonal wrench 3/16 in. (4 mm) at opposite side 
to insert the drain cap, till the drain cap contacts the tip of 
drain cock.

No gap

Hexagonal 

wrench

Drain 

cock

Drain cap

Removal method of drain hose

Remove  the  screw  at  the  left  of  drain 

hose and pull out drain hose.

Installation method of drain hose

Vertically insert the drain hose toward the 

inside, so that the drain fixture (white) can ac-

curately align with the screw hole around the 

drain cock.

After inserting and before replacing,  please 

reinstall and fix the removed screws.

•  Please hold around the joint of the drain hose during working.

•  As the screw is inside, be sure to use screwdriver treated with magnet.

Screw

Drain fixture

Drain hose

Screw hole

Drain cock

Drain hose

Screw

Drain fixture

•  For left piping and left rear piping, align the marks on the wall hook bracket and shape the 

connection pipe.

• Bend the connection piping at a bend radius of 4 in. (100 mm) or more and install no 

more than 1-6/16 in. (35 mm) from the wall.

• After passing the indoor piping and drain hose through the wall hole, hang the indoor unit on 

the hooks at the top and bottom of the wall hook bracket.

Wall hook 

bracket

Alignment marks

Small piping

Connection  

piping

Large piping

[Installing the indoor unit]

•   Hang the indoor unit from the hooks at the top of the wall hook bracket.

•   Insert the spacer, etc. between the indoor unit and the wall hook bracket and separate 

the bottom of the indoor unit from the wall.

Unit: in. (mm)

Indoor unit

Wall hook bracket

(Spacer)

 

 

 

 

 

 

 

Top hooks

Indoor 

unit

(Fitting)

Bottom hooks

Wall hook 

bracket

After hooking the indoor unit to the top hook, hook the fittings of the indoor unit to the 2 

bottom hooks while lowering the unit and pushing it against the wall.

5.6. Flare connection (Pipe connection)

 CAUTION

 Tighten the flare nuts with a torque wrench using the specified tightening method. Oth-

erwise, the flare nuts could break after a prolonged period, causing refrigerant to leak 

and generate hazardous gas if the refrigerant comes into contact with a flame.

5.6.1. Flaring

Use special pipe cutter and flare tool exclusive for R410A.

(1)  Cut the connection pipe to the necessary length with a pipe cutter.

(2)  Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.

(3)  Insert the flare nut (always use the flare nut attached to the indoor unit(s) and outdoor 

unit respectively) onto the pipe and perform the flare processing with a flare tool. Use 

the special R410A flare tool, or the conventional flare tool. Leakage of refrigerant may 

result if other flare nuts are used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

Die

A
Pipe

B

L

Check if [L] is flared uniformly 

and is not cracked or scratched.

9387082098-02_IM.indb   4

21/03/2016   10:12:51

Содержание ASU30RLE

Страница 1: ... a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water damage to walls and floors In an Area with High Winds Securely anchor the outdoor unit down with bolts and a met...

Страница 2: ... erroneous charging with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread diameter for R410A is 1 2 20 UNF Be more careful that foreign matter oil water etc does not enter the piping than with refrigerant R22 models Also when storing the piping securely seal the opening by pinching taping etc When charging the refrigerant take into account the slight ...

Страница 3: ...nimals may urinate on the unit or ammonia may be generated Do not use the unit for special purposes such as storing food raising animals grow ing plants or preserving precision devices or art objects It can degrade the quality of the preserved or stored objects Do not install where there is the warning of combustible gas leakage Do not install the unit near a source of heat steam or flammable gas ...

Страница 4: ...ck Drain cap Removal method of drain hose Remove the screw at the left of drain hose and pull out drain hose Installation method of drain hose Vertically insert the drain hose toward the inside so that the drain fixture white can ac curately align with the screw hole around the drain cock After inserting and before replacing please reinstall and fix the removed screws Please hold around the joint ...

Страница 5: ...CAUTION Connect the piping so that the control box cover can easily be removed for servicing when necessary In order to prevent water from leaking into the control box make sure that the piping is well insulated When the flare nut is tightened properly by your hand hold the body side coupling with a wrench then tighten with a torque wrench See the table below for the flare nut tightening torques T...

Страница 6: ...e terminal screw tightening torques Tightening torque lbf in N m M4 screw 11 to 16 1 2 to 1 8 CAUTION Attach the cable clamp firmly by holding the connection cable and make sure that the clamp is fixed securely Incomplete attachment of the cable clamp might cause a malfunction of the open panel Match the terminal block numbers and connection cable colors with those of the outdoor unit Erroneous wi...

Страница 7: ...ation Vinyl tape Wrap with cloth tape Cloth tape Drain hose Connection cable Pipe Drain hose Drain hose Connection pipe Wall pipe Connection cable Left piping For connection from the left rear Pipe Connection pipe heat insulation Indoor unit pipe heat insulation Bind the pipes together so that there is no gap Seal A is used when the diam eter of gas pipe is Ø12 70 or more Butt connection pipe heat...

Страница 8: ...tricted When function setting is Operation Stop mode 2 Input signal Command OFF ON Operation ON OFF Stop R C disabled 10 1 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25 m 82 ft Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed Output voltage Hi DC12V 2V Lo 0V Permissible current 5...

Страница 9: ...re to insulate the connecting parts when extending the cable Server room control For server room control connect the communication cable to the terminal block following the same procedure as the remote controller cable For details refer to the service instruction for Server room control Note Wire colors may not match Match the numbers on the terminal block of each indoor unit Tab Cable clamper and...

Страница 10: ...ch indoor unit using the Function setting a 3 wire type Function setting RC AD setting Factory setting 00 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD setting in sequence from 00 b 2 wire type Function setting RC AD setting Factory setting 00 Since the remote controller address settings are automatically configured you do not need to configur...

Страница 11: ... buttons to select the setting value Press the MIN HEAT button to switch between the left and right digits 4 Press the MODE button in the order listed to confirm the settings Please confirm that the beep sounds 5 Next please press START STOP button Please confirm that the beep sounds 6 Press the RESET button to cancel the function set ting mode 7 After completing the FUNCTION SETTING be sure to tu...

Страница 12: ...ot set first Room temperature control settings Function 30 31 92 93 will be reset and you must re do them again Heat Insulation condition building insulation Heat insulation conditions differ according to the installed environment Standard insulation 00 allows system to rapidly respond to the cooling or heating load changes High insulation 01 is when the heat insulation structure of the building i...

Страница 13: ...g to the customer in accordance with the operating manual 1 Starting and stopping method operation switching temperature adjustment timer air flow switching and other remote controller operations 2 Air filter removal and cleaning and how to use the air louvers 3 Give the operating manual to the customer 18 ERROR CODES If you use a wireless remote controller the lamp on the photo detector unit will...

Страница 14: ...sure sensor error Suction pressure sensor error High pressure switch error 9 4 Trip detection 9 5 Compressor rotor position detection error permanent stop 9 7 Outdoor unit fan motor 1 error 9 8 Outdoor unit fan motor 2 error 9 9 4 way valve error 9 10 Coil expansion valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes e...

Отзывы: