En-10

11.3. 

Front panel, control box cover replacement

Reinstall by reversing the procedure in “11.1. Front panel, control box cover removal”
(1)   Replace the control box cover and screws.

Screw

Screw

(2)   Open a hole in the front panel for the remote  

controller cable to pass through. 

 

*  Choose from 4 knockout holes marked on  

the inside of the front panel.

(3)  Replace the front cover.

 

Refer to “8.2. Front panel installation”

12. GROUP CONTROL

 

CAUTION

Group control is only possible between units with remote controllers of the same type. 

To confirm the type of remote controller, see the back of the remote controller or  

“2.3. Accessories”.

A number of indoor units can be operated at the same time using a single remote controller.
(1)  Connect up to 16 indoor units in a system.

A

B

C

D

E

I.U.

I.U.

I.U.

I.U.

Remote 

controller

A, B, C, D, E : Remote controller cable.

A+B+C+D+E ≤ 300 m.

Total wiring length of RC

Cross section of cable

328ft (100m) or less

0.01-0.03inch (0.3-0.8mm)(AWG 18-22)

328-656ft (100-200m)

0.02-0.03inch (0.5-0.8mm)(AWG 18-20)

656-984ft (200-300m)

0.03inch (0.8mm)(AWG18)

Example of wiring method (3-wire type)

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

Indoor unit 1

Indoor unit 2

Indoor unit 3

Indoor unit 4

Bus wire

Remote

controller cable

Remote controller

R  W  B

(2)  Set the R.C. address (Function setting)

 

Set the R.C. address of each indoor unit using the Function setting.

(a)  3-wire type

Function setting (RC AD setting)...Factory setting “00”

  When connecting multiple indoor units to 1 standard wired remote controller, set the 

address at RC AD setting in sequence from “00”.

(b) 2-wire type

Function setting (RC AD setting)...Factory setting “00”

Since the remote controller address settings are automatically configured, you do not 

need to configure them.

If configuring manually, it is necessary to configure both the indoor unit and the remote 

controller. For details, please refer to the remote controller installation manual.

 

Example

 

If 4 indoor units are connected.

RC AD SW

00

RC AD SW

01

RC AD SW

02

RC AD SW

03

Indoor unit 1

Remote 

controller

Indoor unit 2

Indoor unit 3

Indoor unit 4

Set the R.C. address in accordance with the table below.

Remote controller address setting

(♦...  Factory setting)

Function  

Number

Setting Value

Setting Description

00

00

Unit no. 0

01

Unit no. 1

02

Unit no. 2

03

Unit no. 3

04

Unit no. 4

05

Unit no. 5

06

Unit no. 6

07

Unit no. 7

08

Unit no. 8

09

Unit no. 9

10

Unit no. 10

11

Unit no. 11

12

Unit no. 12

13

Unit no. 13

14

Unit no. 14

15

Unit no. 15

*  When connecting Polar 3-core wired remote controller, set the remote controller address 

in the order of 0, 1, 2, ....., and 15.

*  When different type of indoor units (such as wall-mounted type and cassette type, cassette 

type and duct type, or other combinations) are connected using group control system, some 
functions may no longer be available.

9387082098-02_IM.indb   10

21/03/2016   10:13:00

Содержание ASU30RLE

Страница 1: ... a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water damage to walls and floors In an Area with High Winds Securely anchor the outdoor unit down with bolts and a met...

Страница 2: ... erroneous charging with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread diameter for R410A is 1 2 20 UNF Be more careful that foreign matter oil water etc does not enter the piping than with refrigerant R22 models Also when storing the piping securely seal the opening by pinching taping etc When charging the refrigerant take into account the slight ...

Страница 3: ...nimals may urinate on the unit or ammonia may be generated Do not use the unit for special purposes such as storing food raising animals grow ing plants or preserving precision devices or art objects It can degrade the quality of the preserved or stored objects Do not install where there is the warning of combustible gas leakage Do not install the unit near a source of heat steam or flammable gas ...

Страница 4: ...ck Drain cap Removal method of drain hose Remove the screw at the left of drain hose and pull out drain hose Installation method of drain hose Vertically insert the drain hose toward the inside so that the drain fixture white can ac curately align with the screw hole around the drain cock After inserting and before replacing please reinstall and fix the removed screws Please hold around the joint ...

Страница 5: ...CAUTION Connect the piping so that the control box cover can easily be removed for servicing when necessary In order to prevent water from leaking into the control box make sure that the piping is well insulated When the flare nut is tightened properly by your hand hold the body side coupling with a wrench then tighten with a torque wrench See the table below for the flare nut tightening torques T...

Страница 6: ...e terminal screw tightening torques Tightening torque lbf in N m M4 screw 11 to 16 1 2 to 1 8 CAUTION Attach the cable clamp firmly by holding the connection cable and make sure that the clamp is fixed securely Incomplete attachment of the cable clamp might cause a malfunction of the open panel Match the terminal block numbers and connection cable colors with those of the outdoor unit Erroneous wi...

Страница 7: ...ation Vinyl tape Wrap with cloth tape Cloth tape Drain hose Connection cable Pipe Drain hose Drain hose Connection pipe Wall pipe Connection cable Left piping For connection from the left rear Pipe Connection pipe heat insulation Indoor unit pipe heat insulation Bind the pipes together so that there is no gap Seal A is used when the diam eter of gas pipe is Ø12 70 or more Butt connection pipe heat...

Страница 8: ...tricted When function setting is Operation Stop mode 2 Input signal Command OFF ON Operation ON OFF Stop R C disabled 10 1 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25 m 82 ft Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed Output voltage Hi DC12V 2V Lo 0V Permissible current 5...

Страница 9: ...re to insulate the connecting parts when extending the cable Server room control For server room control connect the communication cable to the terminal block following the same procedure as the remote controller cable For details refer to the service instruction for Server room control Note Wire colors may not match Match the numbers on the terminal block of each indoor unit Tab Cable clamper and...

Страница 10: ...ch indoor unit using the Function setting a 3 wire type Function setting RC AD setting Factory setting 00 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD setting in sequence from 00 b 2 wire type Function setting RC AD setting Factory setting 00 Since the remote controller address settings are automatically configured you do not need to configur...

Страница 11: ... buttons to select the setting value Press the MIN HEAT button to switch between the left and right digits 4 Press the MODE button in the order listed to confirm the settings Please confirm that the beep sounds 5 Next please press START STOP button Please confirm that the beep sounds 6 Press the RESET button to cancel the function set ting mode 7 After completing the FUNCTION SETTING be sure to tu...

Страница 12: ...ot set first Room temperature control settings Function 30 31 92 93 will be reset and you must re do them again Heat Insulation condition building insulation Heat insulation conditions differ according to the installed environment Standard insulation 00 allows system to rapidly respond to the cooling or heating load changes High insulation 01 is when the heat insulation structure of the building i...

Страница 13: ...g to the customer in accordance with the operating manual 1 Starting and stopping method operation switching temperature adjustment timer air flow switching and other remote controller operations 2 Air filter removal and cleaning and how to use the air louvers 3 Give the operating manual to the customer 18 ERROR CODES If you use a wireless remote controller the lamp on the photo detector unit will...

Страница 14: ...sure sensor error Suction pressure sensor error High pressure switch error 9 4 Trip detection 9 5 Compressor rotor position detection error permanent stop 9 7 Outdoor unit fan motor 1 error 9 8 Outdoor unit fan motor 2 error 9 9 4 way valve error 9 10 Coil expansion valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes e...

Отзывы: