En-11

13. SELECTING THE REMOTE CONTROLLER CUSTOM CODE

When two or more air conditioners are installed in a room and the remote controller is 
operating an air conditioner other than the one you wish to set, change the custom code 
of the remote controller to operate only the air conditioner you wish to set (4 selections 
possible).

Selecting the Remote Controller Custom Code

Use the following steps to select the custom code of the remote controller. (Note that the 
air conditioner cannot receive a signal if the air conditioner has not been set for the match-
ing custom code.)
(1)   Press the START/STOP (

) button until only the clock 

is displayed on the remote controller display.

(2)   Press the MODE button for at least 5 seconds to display 

the current custom code (initially set to A).

(3)   Press the SET TEMP. (  /  ) buttons to change the 

custom code between A→B→C→D. 

Match the code on the display to the air conditioner 

custom code.

(4)   Press the MODE button again to return to the clock 

display. The custom code will be changed.

•  If no buttons are pressed within 30 seconds after the custom code is displayed, the 

system returns to the original clock display. In this case, start again from step 1.

• The air conditioner custom code is set to A prior to shipment.

14. FUNCTION SETTING

Perform the “FUNCTION SETTING” according to the installation conditions using the remote 
controller.

 CAUTION

•  Confirm whether the wiring work for Outdoor unit has been finished.

•  Confirm that the cover for the electrical enclosure on the outdoor unit is in place.

•  This procedure changes to the function settings used to control the indoor unit according 

to the installation conditions. Incorrect settings can cause the indoor unit to malfunction.

•  After the power is turned on, perform the “FUNCTION SETTING” according to the 

installation conditions using the remote controller.

•  The settings may be selected between the following two: Function Number or Setting 

Value.

•  Settings will not be changed if invalid numbers or setting values are selected.
•  Match the custom code of the indoor unit and the custom code of the remote controller. 

(See “11. SELECTING THE REMOTE CONTROLLER CUSTOM CODE”.)

Entering the Function Setting Mode

While pressing the POWERFUL button and SET TEMP. ( ) button simultaneously, press 
the RESET button to enter the function setting mode.

Selecting the Function Number and Setting Value

(1)   Press  the  SET TEMP.  (   /  )  buttons  to  select 

the function number. (Press the MIN. HEAT button 

to switch between the left and right digits.)

(2)   Press the POWERFUL button to proceed to setting 

the value. (Press the POWERFUL button again to 

return to the function number selection.)

(3)   Press  the  SET TEMP.  (   /  )  buttons  to  select 

the setting value. (Press the MIN. HEAT button to 

switch between the left and right digits.)

(4)   Press the MODE button, in the order listed to confirm 

the settings.

Please confirm that the beep sounds.

(5)   Next, please press START/STOP (

) button.

Please confirm that the beep sounds.

(6)   Press the RESET button to cancel the function set-

ting mode.

(7)   After completing the FUNCTION SETTING, be sure to turn off the power and turn it 

on again.

 CAUTION

After turning off the power, wait 30 seconds or more before turning on it again.
The Function Setting does not become active unless the power is turned off then on 

again.

Function number

Setting 

value

14.1. 

Function details

Filter Sign

Select appropriate intervals for displaying the filter sign on the indoor unit according to the 

estimated amount of dust in the air of the room.

If the indication is not required, select “No indication” (03).

(♦...  Factory setting)

Function Number

Setting 

Value

Setting Description

11

00

Standard (400 hours)

01

Long interval (1000 hours)

02

Short interval (200 hours)

03

No indication

Auto Restart

Enable or disable automatic restart after a power interruption.

(♦...  Factory setting)

Function Number

Setting 

Value

Setting Description

40

00

Enable

01

Disable

* Auto restart is an emergency function such as for power outage etc. Do not attempt to 

use this function in normal operation. Be sure to operate the unit by remote controller or 

external device.

Room temperature sensor switching

(Only for Wired remote controller)

When using the Wired remote controller temperature sensor, change the setting to “Both” 

(01).

(♦...  Factory setting)

Function Number

Setting 

Value

Setting Description

42

00

Indoor unit

01

Both

00: Sensor on the indoor unit is active.

01: Sensors on both indoor unit and wired remote controller are active.

* Remote controller sensor must be turned on by using the remote controller.

Remote controller custom code

(Only for wireless remote controller)
The indoor unit custom code can be changed.
Select the appropriate custom code.

(♦...  Factory setting)

Function Number

Setting 

Value

Setting Description

44

00

A

01

B

02

C

03

D

External input control

“Operation/Stop” mode or “Forced stop” mode can be selected.

(♦...  Factory setting)

Function Number

Setting 

Value

Setting Description

46

00

Operation/Stop mode 1

01

(Setting prohibited)

02

Forced stop mode

03

Operation/Stop mode 2

Room temperature sensor switching (Aux.)

To use the temperature sensor on the wired remote controller only, change the setting to 
“Wired remote controller” (01). This function will only work if the function setting 42 is set 
at “Both” (01)
When the setting value is set to “Both” (00), more suitable control of the room temperature 
by setting function setting 30 and 31 too.

(♦...  Factory setting)

Function Number

Setting 

Value

Setting Description

48

00

Both

01

Wired remote controller

9387082098-02_IM.indb   11

21/03/2016   10:13:01

Содержание ASU30RLE

Страница 1: ... a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water damage to walls and floors In an Area with High Winds Securely anchor the outdoor unit down with bolts and a met...

Страница 2: ... erroneous charging with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread diameter for R410A is 1 2 20 UNF Be more careful that foreign matter oil water etc does not enter the piping than with refrigerant R22 models Also when storing the piping securely seal the opening by pinching taping etc When charging the refrigerant take into account the slight ...

Страница 3: ...nimals may urinate on the unit or ammonia may be generated Do not use the unit for special purposes such as storing food raising animals grow ing plants or preserving precision devices or art objects It can degrade the quality of the preserved or stored objects Do not install where there is the warning of combustible gas leakage Do not install the unit near a source of heat steam or flammable gas ...

Страница 4: ...ck Drain cap Removal method of drain hose Remove the screw at the left of drain hose and pull out drain hose Installation method of drain hose Vertically insert the drain hose toward the inside so that the drain fixture white can ac curately align with the screw hole around the drain cock After inserting and before replacing please reinstall and fix the removed screws Please hold around the joint ...

Страница 5: ...CAUTION Connect the piping so that the control box cover can easily be removed for servicing when necessary In order to prevent water from leaking into the control box make sure that the piping is well insulated When the flare nut is tightened properly by your hand hold the body side coupling with a wrench then tighten with a torque wrench See the table below for the flare nut tightening torques T...

Страница 6: ...e terminal screw tightening torques Tightening torque lbf in N m M4 screw 11 to 16 1 2 to 1 8 CAUTION Attach the cable clamp firmly by holding the connection cable and make sure that the clamp is fixed securely Incomplete attachment of the cable clamp might cause a malfunction of the open panel Match the terminal block numbers and connection cable colors with those of the outdoor unit Erroneous wi...

Страница 7: ...ation Vinyl tape Wrap with cloth tape Cloth tape Drain hose Connection cable Pipe Drain hose Drain hose Connection pipe Wall pipe Connection cable Left piping For connection from the left rear Pipe Connection pipe heat insulation Indoor unit pipe heat insulation Bind the pipes together so that there is no gap Seal A is used when the diam eter of gas pipe is Ø12 70 or more Butt connection pipe heat...

Страница 8: ...tricted When function setting is Operation Stop mode 2 Input signal Command OFF ON Operation ON OFF Stop R C disabled 10 1 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25 m 82 ft Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed Output voltage Hi DC12V 2V Lo 0V Permissible current 5...

Страница 9: ...re to insulate the connecting parts when extending the cable Server room control For server room control connect the communication cable to the terminal block following the same procedure as the remote controller cable For details refer to the service instruction for Server room control Note Wire colors may not match Match the numbers on the terminal block of each indoor unit Tab Cable clamper and...

Страница 10: ...ch indoor unit using the Function setting a 3 wire type Function setting RC AD setting Factory setting 00 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD setting in sequence from 00 b 2 wire type Function setting RC AD setting Factory setting 00 Since the remote controller address settings are automatically configured you do not need to configur...

Страница 11: ... buttons to select the setting value Press the MIN HEAT button to switch between the left and right digits 4 Press the MODE button in the order listed to confirm the settings Please confirm that the beep sounds 5 Next please press START STOP button Please confirm that the beep sounds 6 Press the RESET button to cancel the function set ting mode 7 After completing the FUNCTION SETTING be sure to tu...

Страница 12: ...ot set first Room temperature control settings Function 30 31 92 93 will be reset and you must re do them again Heat Insulation condition building insulation Heat insulation conditions differ according to the installed environment Standard insulation 00 allows system to rapidly respond to the cooling or heating load changes High insulation 01 is when the heat insulation structure of the building i...

Страница 13: ...g to the customer in accordance with the operating manual 1 Starting and stopping method operation switching temperature adjustment timer air flow switching and other remote controller operations 2 Air filter removal and cleaning and how to use the air louvers 3 Give the operating manual to the customer 18 ERROR CODES If you use a wireless remote controller the lamp on the photo detector unit will...

Страница 14: ...sure sensor error Suction pressure sensor error High pressure switch error 9 4 Trip detection 9 5 Compressor rotor position detection error permanent stop 9 7 Outdoor unit fan motor 1 error 9 8 Outdoor unit fan motor 2 error 9 9 4 way valve error 9 10 Coil expansion valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes e...

Отзывы: