En-6

Earth 

(Ground) 

screw

Indoor unit terminal block

Disconnect switch

Please connect 

it to the specified 

terminal.

Outdoor unit or 

Branch box

 Terminal block for the optional remote controller

•   To connect the indoor unit wires to the terminal correctly, refer to the figure for proper 

length. 

14AWG

Earth (Ground) wire

Conduit holder

Conduit connector

9-1/16 

(230)

9-7/16 

(240)

6.3. How to the install the indoor unit wire harness

(1) Remove the screws, then remove the conduit holder.

(2) Fasten the indoor unit wire harness to the conduit holder using the lock nut.

  IMPORTANT: Refer to [6.1. Wiring system diagram] about the length of indoor unit wire 

harness.

(3) Use the screws to install the conduit holder provide with the indoor unit.

(4) Remove the screws, then remove the cable clamper.

(5) Connect indoor unit wire harness to the terminal.

  Refer to the wiring diagram

(6) Use the screws to install the cable clamper.

Lock nut

Conduit holder

Conduit connector

6.4.  How to connect wiring to the terminals

Caution when wiring cable

When stripping off the insulation of a lead wire, always use a special tool such as a wire 

stripper. If there is no special tool available, carefully strip the insulation with a knife etc.

(1)  Use ring terminals with insulating sleeves as shown in the figure below to connect to 

the terminal block.

(2)  Securely clamp the ring terminals to the wires using an appropriate tool so that the 

wires do not come loose.

Strip : 3/8 in. (10 mm)

Ring terminal

Sleeve

(3)  Use the specified wires, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-

driver that is too small, otherwise, the screw heads may be damaged and prevent the 

screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.

Screw with special washer

Wire

Ring terminal

Terminal blocks

Wire

Screw with special washer

Ring terminal

(6)  See the table below for the terminal screw tightening torques.

Tightening torque [lbf·in (N·m)]

M4 screw

11 to 16 (1.2 to 1.8)

 CAUTION

•  Attach the cable clamp firmly by holding the connection cable, and make sure that the 

clamp is fixed securely. 

Incomplete attachment of the cable clamp might cause a malfunction of the open 

panel.

•  Match the terminal block numbers and connection cable colors with those of the 

outdoor unit.

Erroneous wiring may cause burning of the electric parts.

•  Connect the connection cables firmly to the terminal block. Imperfect installation may 

cause a fire.

•  Always fasten the outside covering of the connection cable with the cable clamp. 

(If the insulator is chafed, electric discharge may occur.)

•  Always connect the ground wire.

•  Do not use the earth screw of the indoor unit for the connection other than a specified 

outdoor unit.

7.  FINISHING 

 (1)  Insulate between pipes.

•  Insulate suction and discharge pipes separately.

•  For rear, right, and bottom piping, overlap the connection pipe heat insulation and 

indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap.

•  For left and left rear piping, butt the connection pipe heat insulation and indoor unit 

pipe heat insulation together and bind them with and vinyl tape so that there is no gap.

•  For left and left rear piping, wrap the area which accommodates the rear piping 

housing section with cloth tape.

•  For left and left rear piping, bind the connection cable to the top of the pipe with 

vinyl tape.

•  For left and left rear piping, bundle the piping and drain hose together by wrapping 

them with cloth tape over the range within which they fit into the rear piping 

housing section.

 (2)  Temporarily fasten the connection cable along the connection pipe with vinyl tape. 

(Wrap to about 1/3 the width of the tape from the bottom of the pipe so that water 

does not enter.)

 (3)  Fasten the connection pipe to the outside wall with a saddle, etc.

 (4)  Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain 

water and wind cannot blow in.

 (5)  Fasten the drain hose to the outside wall, etc.

*Locally purchased

Pipe

Saddle*

Outside wall cap*

Sealer putty*

(Outdoors)

Wall

Unit: in. (mm)

Screw

9387082098-02_IM.indb   6

21/03/2016   10:12:54

Содержание ASU30RLE

Страница 1: ... a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water damage to walls and floors In an Area with High Winds Securely anchor the outdoor unit down with bolts and a met...

Страница 2: ... erroneous charging with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread diameter for R410A is 1 2 20 UNF Be more careful that foreign matter oil water etc does not enter the piping than with refrigerant R22 models Also when storing the piping securely seal the opening by pinching taping etc When charging the refrigerant take into account the slight ...

Страница 3: ...nimals may urinate on the unit or ammonia may be generated Do not use the unit for special purposes such as storing food raising animals grow ing plants or preserving precision devices or art objects It can degrade the quality of the preserved or stored objects Do not install where there is the warning of combustible gas leakage Do not install the unit near a source of heat steam or flammable gas ...

Страница 4: ...ck Drain cap Removal method of drain hose Remove the screw at the left of drain hose and pull out drain hose Installation method of drain hose Vertically insert the drain hose toward the inside so that the drain fixture white can ac curately align with the screw hole around the drain cock After inserting and before replacing please reinstall and fix the removed screws Please hold around the joint ...

Страница 5: ...CAUTION Connect the piping so that the control box cover can easily be removed for servicing when necessary In order to prevent water from leaking into the control box make sure that the piping is well insulated When the flare nut is tightened properly by your hand hold the body side coupling with a wrench then tighten with a torque wrench See the table below for the flare nut tightening torques T...

Страница 6: ...e terminal screw tightening torques Tightening torque lbf in N m M4 screw 11 to 16 1 2 to 1 8 CAUTION Attach the cable clamp firmly by holding the connection cable and make sure that the clamp is fixed securely Incomplete attachment of the cable clamp might cause a malfunction of the open panel Match the terminal block numbers and connection cable colors with those of the outdoor unit Erroneous wi...

Страница 7: ...ation Vinyl tape Wrap with cloth tape Cloth tape Drain hose Connection cable Pipe Drain hose Drain hose Connection pipe Wall pipe Connection cable Left piping For connection from the left rear Pipe Connection pipe heat insulation Indoor unit pipe heat insulation Bind the pipes together so that there is no gap Seal A is used when the diam eter of gas pipe is Ø12 70 or more Butt connection pipe heat...

Страница 8: ...tricted When function setting is Operation Stop mode 2 Input signal Command OFF ON Operation ON OFF Stop R C disabled 10 1 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25 m 82 ft Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed Output voltage Hi DC12V 2V Lo 0V Permissible current 5...

Страница 9: ...re to insulate the connecting parts when extending the cable Server room control For server room control connect the communication cable to the terminal block following the same procedure as the remote controller cable For details refer to the service instruction for Server room control Note Wire colors may not match Match the numbers on the terminal block of each indoor unit Tab Cable clamper and...

Страница 10: ...ch indoor unit using the Function setting a 3 wire type Function setting RC AD setting Factory setting 00 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD setting in sequence from 00 b 2 wire type Function setting RC AD setting Factory setting 00 Since the remote controller address settings are automatically configured you do not need to configur...

Страница 11: ... buttons to select the setting value Press the MIN HEAT button to switch between the left and right digits 4 Press the MODE button in the order listed to confirm the settings Please confirm that the beep sounds 5 Next please press START STOP button Please confirm that the beep sounds 6 Press the RESET button to cancel the function set ting mode 7 After completing the FUNCTION SETTING be sure to tu...

Страница 12: ...ot set first Room temperature control settings Function 30 31 92 93 will be reset and you must re do them again Heat Insulation condition building insulation Heat insulation conditions differ according to the installed environment Standard insulation 00 allows system to rapidly respond to the cooling or heating load changes High insulation 01 is when the heat insulation structure of the building i...

Страница 13: ...g to the customer in accordance with the operating manual 1 Starting and stopping method operation switching temperature adjustment timer air flow switching and other remote controller operations 2 Air filter removal and cleaning and how to use the air louvers 3 Give the operating manual to the customer 18 ERROR CODES If you use a wireless remote controller the lamp on the photo detector unit will...

Страница 14: ...sure sensor error Suction pressure sensor error High pressure switch error 9 4 Trip detection 9 5 Compressor rotor position detection error permanent stop 9 7 Outdoor unit fan motor 1 error 9 8 Outdoor unit fan motor 2 error 9 9 4 way valve error 9 10 Coil expansion valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes e...

Отзывы: