2-33. E: 99. 4-way valve error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
9 time flash
Timer indicator
9 time flash
Economy indicator
Continuous flash
Error code
E: 99
outdoor unit
Refer to “Error code table (Outdoor unit: for 34 model
only)” on page 1
Detective actuator
Indoor unit
main PCB
When the indoor heat exchanger temperature is
compared with the room temperature, and either
following condition is detected continuously two times,
the compressor stops.
Indoor heat exchanger temp. - Room temp. > 10 °C
(Cooling or Dry operation)
Indoor heat exchanger temp. - Room temp. < -10 °C
(Heating operation)
If the same operation is repeated 5 times, the
compressor stops permanently.
Heat exchanger temperature
thermistor
Room temperature thermistor
4-way valve
Forecast of cause
Air filter clogged
Connector connection failure
Thermistor failure
Coil failure
4-way valve failure
Controller PCB failure
Check point 1. Check air filter condition
Check air filter dirty.
→ If the air filter dirty, clean up the air filter.
↓
Check point 2. Check connection of connector
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if thermistor cable is open.
→ Upon correcting the removed connector or mis-wiring, reset the power.
↓
Check point 3. Check each thermistor
•
Isn’t it fallen off the holder?
•
Is there a cable pinched?
Check characteristics of room thermistor and indoor unit heat exchanger thermistor.
For the thermistor resistance value, refer to
"Thermistor resistance values"
→ If defective, replace the thermistor.
↓
2-33. E: 99. 4-way valve error (Outdoor unit)
- (03-48) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание AOTG30KMTC
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2019 06 27 SR_CH01_AS004EF_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 05 12 SR_CH02_AS004EF_05 ...
Страница 35: ...3 TROUBLESHOOTING 2020 05 08 SR_CH03_AS004EF_02 ...
Страница 38: ......
Страница 128: ...6 2 Outdoor unit 03 90 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 129: ...4 CONTROL AND FUNCTIONS 2020 05 08 SR_CH04_AS004EF_02 ...
Страница 132: ......
Страница 163: ...5 FILED WORKING 2019 07 24 SR_CH05_AS004EF_01 ...