Table 2. Standard value is changed by the tool specification (Type A and B are same value)
Terminal
Resistance value
Multimeter
(+)
(-)
L2
P
1.32 MΩ/0.66 MΩ
(Ref. value 1/Ref. value 2)
P
L2
1.01 MΩ/0.76 MΩ
(Ref. value 1/Ref. value 2)
: By kind of multimeter, the value may change significantly.
Specifications of
multi meter
Ref. value 1
Ref. value 2
Manufacturer
FLUKE
SANWA
Model name
FLUKE11
PM3
Power source
DC 9 V
DC 3 V
If it is abnormal, replace active filter module.
Check point 2. Check the output DC voltage (between P and N)
Check the output DC voltage (between P and N) or compressor stopping and operating.
→ If the output voltage of compressor operating is less than the output voltage of com-
pressor stopping, active filter module is defective.
Replace the active filter module.