11) Control switching of external heaters
Sets the control method for external heater to be used.
For details, refer to
Chapter 3-4. "Details of function"
Function
number
Setting value
Setting description
Factory
setting
61
00
Auxiliary heater control 1
♦
01
Auxiliary heater control 2
02
Heat pump prohibition control
03
Auxiliary heater control by outdoor temperature 1
04
Auxiliary heater control by outdoor temperature 2
12) Operating temperature switching of external heaters
Sets the temperature conditions when the external heater is ON.
For details, refer to
Chapter 3-4. "Details of function"
Function
number
Setting
value
Setting description
Factory
setting
Setting value of function 61:
00, 01
02, 03, 04
Heater: On
Heater: Off
Heater: On
Heater: Off
62
00
-3 °C
-1 °C
-0.5 °C
0.5 °C
♦
01
-2 °C
-1 °C
-1 °C
0.5 °C
02
-2 °C
-1 °C
-2 °C
0.5 °C
03
-3 °C
-1 °C
-3 °C
0.5 °C
04
-4 °C
-1 °C
-4 °C
0.5 °C
05
-5 °C
-1 °C
-5 °C
0.5 °C
13) Outdoor temperature zone boundary temperature A
Setting required if changing of the outdoor temperature setting for heat pump prohibition zone is re-
quired when auxiliary heater control by outdoor temperature 1 and 2 are performed on the indoor
unit. For details, refer to
Chapter 3-4. "Details of function"
Function number
Setting value
Setting description
Factory setting
66
00
-20 °C
♦
01
-18 °C
02
-16 °C
03
-14 °C
04
-12 °C
05
-10 °C
06
-8 °C
07
-6 °C
08
-4 °C
1-1. Function settings by using remote controller
- (05-7) -
1. Function settings (For indoor unit)
FIELD
WORKING
FIELD
WORKING
Содержание AOTG30KMTC
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2019 06 27 SR_CH01_AS004EF_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 05 12 SR_CH02_AS004EF_05 ...
Страница 35: ...3 TROUBLESHOOTING 2020 05 08 SR_CH03_AS004EF_02 ...
Страница 38: ......
Страница 128: ...6 2 Outdoor unit 03 90 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 129: ...4 CONTROL AND FUNCTIONS 2020 05 08 SR_CH04_AS004EF_02 ...
Страница 132: ......
Страница 163: ...5 FILED WORKING 2019 07 24 SR_CH05_AS004EF_01 ...