1. Specifications
1-1. Indoor unit
Type
Wall mounted
Inverter heat pump
Model name
ASTG30KMTC
ASTG34KMTC
Power supply
240 V ~ 50 Hz
Power supply intake
Outdoor unit
Available voltage range
198—264 V
Star rating index
10-star standard
Cooling
2.0
2.0
Heating
3.0
2.5
Capacity
Cooling
Rated
kW
8.50
9.40
Btu/h
29,000
32,000
Min.—Max.
kW
2.9—10.5
2.9—11.2
Btu/h
9,900—35,800
9,900—38,200
Heating
Rated
kW
9.00
10.30
Btu/h
30,700
35,100
Min.—Max.
kW
2.2—11.2
2.7—11.7
Btu/h
7,500—38,200
9,200—39,900
Input power
Cooling
Rated
kW
2.46
2.78
Min.—Max.
0.58—3.85
0.59—4.03
Heating
Rated
2.34
2.84
Min.—Max.
0.50—4.01
0.60—4.24
Fan
W
63
63
Current
Cooling
Rated
A
10.4
11.7
Heating
10.1
11.9
EER
Cooling
kW/kW
3.45
3.38
COP
Heating
3.84
3.63
Sensible capacity
Cooling
kW
6.00
6.95
Power factor
Cooling
%
98.5
99
Heating
97
99
Moisture removal
L/h (pints/h)
2.5 (4.4)
3.5 (6.2)
Maximum operating current *1
Cooling
A
17.0
19.5
Heating
17.0
19.5
Fan
Airflow rate
Cooling
HIGH
l/s (m
3
/h)
389 (1,400)
MED
319 (1,150)
LOW
256 (920)
QUIET
200 (720)
Heating
HIGH
389 (1,400)
MED
319 (1,150)
LOW
256 (920)
QUIET
200 (720)
Type × Q'ty
Cross flow fan × 1
Motor output
W
61
Sound pressure level *2
Cooling
HIGH
dB (A)
51
52
MED
46
47
LOW
40
41
QUIET
33
34
Heating
HIGH
51
51
MED
44
44
LOW
39
38
QUIET
33
33
Heat exchanger
Dimensions (H × W × D)
mm
Main: 448 × 900 × 30
Sub1: 126 × 900 × 13.3
Sub2: 84 × 900 × 13.3
Fin pitch
Main: 1.2, Sub: 1.4
Rows × Stages
Main: 3 × 28, Sub1: 1 × 6, Sub2: 1 × 4
Pipe type
Copper tube
Fin type
Aluminum
Enclosure
Material
Polystyrene
Color
White
Approximate color of Munsell N 9.25/
Dimensions
(H × W × D)
Net
mm
340 × 1,150 × 280
Gross
405 × 1,270 × 450
Weight
Net
kg
18.5
Gross
24
Connection pipe
Size
Liquid
mm (in)
Ø 9.52 (Ø 3/8)
Gas
Ø 15.88 (Ø 5/8)
Method
Flare
Drain hose
Material
PVC
Size
mm
Ø 13.8 (I.D.), Ø 15.8 to Ø 16.7 (O.D.)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Remote controller
Wireless or Mobile app (FGLair*3) (Wired [option])
International Protection rating
IPX0
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
• *2: Sound pressure level:
–
Measured values in manufacturer’s anechoic chamber.
–
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play store or on App Store. For details, refer to the setting manual.
1-1. Indoor unit
- (01-1) -
1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION
Содержание AOTG30KMTC
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2019 06 27 SR_CH01_AS004EF_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 05 12 SR_CH02_AS004EF_05 ...
Страница 35: ...3 TROUBLESHOOTING 2020 05 08 SR_CH03_AS004EF_02 ...
Страница 38: ......
Страница 128: ...6 2 Outdoor unit 03 90 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 129: ...4 CONTROL AND FUNCTIONS 2020 05 08 SR_CH04_AS004EF_02 ...
Страница 132: ......
Страница 163: ...5 FILED WORKING 2019 07 24 SR_CH05_AS004EF_01 ...