
2-20. E: 64. Active filter voltage error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
6 time flash
Timer indicator
4 time flash
Economy indicator
Continuous flash
Error code
E: 64
outdoor unit
Refer to “Error code table (Outdoor unit: for 34 model
only)” on page 1
Detective actuator
Outdoor unit
Main PCB
•
When inverter input DC voltage is higher than 430
V or lower than 110 V
•
When a momentary power cut off occurred on low
voltage
Air filter module
Forecast of cause
External cause
Connector connection failure
Main PCB failure
Active filter module failure
Check point 1. Check external cause at indoor and outdoor (Voltage drop or Noise)
•
Instant drop: Check if there is a large load electric apparatus in the same circuit.
•
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
•
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
↓
Check point 2. Check connection of Connector
Upon correcting the removed connector or mis-
wiring, reset the power.
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open.
↓
Check point 3. Check active filter module
Check active filter module. (Refer to active filter module in
75.)
→ If active filter module is abnormal, replace it
↓
Check point 4. Replace main PCB
If check point 1 to 3 do not improve the symptom, change main PCB.
↓
End
2-20. E: 64. Active filter voltage error (Outdoor unit)
- (03-33) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание AOTG30KMTC
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2019 06 27 SR_CH01_AS004EF_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 05 12 SR_CH02_AS004EF_05 ...
Страница 35: ...3 TROUBLESHOOTING 2020 05 08 SR_CH03_AS004EF_02 ...
Страница 38: ......
Страница 128: ...6 2 Outdoor unit 03 90 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 129: ...4 CONTROL AND FUNCTIONS 2020 05 08 SR_CH04_AS004EF_02 ...
Страница 132: ......
Страница 163: ...5 FILED WORKING 2019 07 24 SR_CH05_AS004EF_01 ...