01-20
6. HEATING OVERLOAD PROTECTION
On heating mode, the compressor frequency is controlled as following based on the
detection value of the pressure sensor.
(Fig.13 : Heating Overload Protection Control)
4.1MPa
(65
°C)
Compressor is OFF
The compressor frequency is
decreased 7rps every 60 seconds.
3.3MPa
(55°C)
3.0MPa
(50°C)
2.8MPa
(48°C)
Stable range
Release
The compressor frequency is
decreased 1rps every 60 seconds.
Release
- 20
°C
Cooling
Heating
1-20. COMPRESSOR STOP CONTROL
When the detection value of outdoor temperature sensor is lower than temperature
in the table below, the compressor is stopped.
(Table 18 : Operation temperature of compressor stop control)
Operation
temperature
Temperature
The fan motor for Fresh Air is operated in synchronization with the indoor fan operation
as shown in Fig.14.
1-21. FRESH AIR CONTROL
(Fig.14 : Fresh Air control)
ON
OFF
ON
OFF
Fan motor
(Indoor unit)
Control signal
(for Fresh Air)
12V
Condensing pressure
(Indoor heat ex. temp.)
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание AOG60LATT