Thermistor
02-39
Check Point : Check Thermistor resistance value
Remove connector and check Thermistor resistance value.
Temperature
[°C]
Resistance Value [ k ]
Thermistor A
Thermistor B
Thermistor C
Thermistor D
- 30
- 25
- 20
- 15
- 10
- 5
0
5
10
15
20
25
30
40
50
60
70
80
90
100
110
120
1013.1
729.1
531.6
392.3
292.9
221.1
168.6
129.8
100.9
79.1
62.5
49.8
40.0
26.3
17.8
12.3
8.7
6.3
4.6
3.4
2.6
2.0
95.6
68.9
50.3
37.2
27.8
21.0
16.1
12.4
9.6
7.6
6.0
4.8
3.8
2.5
1.7
1.2
0.8
0.6
---
---
---
---
224.3
159.7
115.2
84.2
62.3
46.6
35.2
26.9
20.7
16.1
12.6
10.0
8.0
5.2
3.5
2.4
1.6
1.2
---
---
---
---
94.3
67.9
49.6
36.7
27.4
20.7
15.8
12.2
9.5
7.5
5.9
4.7
3.8
2.5
1.7
1.2
0.8
0.6
0.4
---
---
---
Applicable
Thermistors
Discharge temp. TH
Compressor temp. TH
Outdoor temp. TH
Heat sink temp. TH
(PFC/ INV)
Heat exchanger. TH
(MID/ OUT)
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание AOG60LATT
Страница 32: ...AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 33: ...2 TROUBLE SHOOTING R410A DUCT type INVERTER AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 74: ...AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 75: ...3 DISASSEMBLY PROCESS R410A DUCT type INVERTER AMP Air Conditioning www ampair co uk sales ampair co uk ...