1-3. DRY OPERATION
1-3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to set temperature and room
temperature variation which the room temperature sensor of the indoor unit has detected
as shown in the Table 3.
( Table 3 : Compressor frequency )
( Fig.2 : Compressor Control based on Room Temperature )
01-03
Ts : Setting temperature
Ts+0.5°C
Ts+1.5°C
Operating
frequency
41rps
X zone
J zone
0rps
Y zone
When the room
temperature drops
When the room
temperature rises
X zone
J zone
Y zone
Ts-1.5°C
Ts-0.5°C
( Fig.3 : Indoor Fan Control )
AO* G60LATT
10
30
60
360
120
360
120
10
30
(sec)
OFF
S-Lo
Lo
OFF
Setting air flow
Compressor
ON
AMP Air Conditioning