01-27
• In this mode, the history of abnormality that occurred in the past can be confirmed.
(Table : 24 Procedure for History Mode )
Procedure
Operation
Power
Mode
1
2
3
4
During status display, press the MODE SWITCH 2 times.
(Status display : Outdoor unit is stopping and no error)
Press the ENTER SWITCH, Error code is displayed by
lighting LED. (Refer to Table : 21)
When the POWER / MODE LED blinking 2 times,
press the ENTER SWITCH.
: Light ON
: Light OFF
: Light ON
: Blinking
2 : 2 Times Blinking
n : n Times Blinking
1 ~ : 1~ 15 Times Blinking
15
1-25-3 Error history mode
(Table : 25 Error Code)
Error
L1
L2
L3
L7
L6
L5
L4
2
2
2
2
n
n
2
Press the SELECT SWITCH and adjust to DISPLAY ITEM
(from L1 to L4) that you want to confirm. (Refer to Table : 17)
POWER
ERROR
TEST
RUN
PUMP
DOWN
LOW NOISE
PEAK CUT
Description
MODE
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
(L7)
1
1
Serial forward transmission error immediately after operation
Serial forward transmission error during operation
2
2
Indoor unit capacity error
5
15
Indoor unit error
6
1
Over voltage
Power supply frequency error
2
Outdoor unit PCB model information error
PFC communication error
3
Inverter error
4
PFC AD detection error
PFC hardware error
5
IPM error (Trip terminal L error)
8
Rush current limiting resister temp rise protection
7
1
Discharge temp. sensor error
2
Compressor temp. sensor error
3
Heat Ex. middle temp. sensor error
Outdoor unit Heat Ex. liquid temp. sensor error
4
Outdoor temp. sensor error
7
Heat sink temp. sensor error
PFC heat sink temp. sensor error
8
4
Current sensor 1 error (stoppage permanently)
6
High pressure switch 1 error
Pressure sensor error
9
4
Trip detection (stoppage permanently)
5
Compressor motor control error (stoppage permanently)
Compressor motor loss of synchronization (stoppage permanently)
7
Outdoor unit fan motor 1 error (Duty error)
8
Outdoor unit fan motor 2 error (Duty error)
9
4-way valve error
10
1
Discharge temp. 1 error (stoppage permanently)
3
Compressor 1 temp. error (stoppage permanently)
5
Low pressure error
Note.
Selecting display items can be done by pressing the SELECT SWITCH. (Return to Procedure 3)
When the EXIT SWITCH is pressed, this mode ends and returns to the status display.
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание AOG60LATT
Страница 32: ...AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 33: ...2 TROUBLE SHOOTING R410A DUCT type INVERTER AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 74: ...AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 75: ...3 DISASSEMBLY PROCESS R410A DUCT type INVERTER AMP Air Conditioning www ampair co uk sales ampair co uk ...