Refer to error code table.
Inverter Error
YES
NO
OK
Check Point 1-2 : External cause
Inverter PCB
Error information received from Inverter PCB
1. External cause. 2. Power supply to Filter PCB to Inverter PCB wiring disconnection, open
3. Filter PCB failure 4. Inverter PCB failure
Check if temporary voltage drop was not generated.
Check if temporary open was not generated.
Check if ground is connected correctly or there are no related cables near the
power line.
Check Point 2 : Check the wiring (Power supply to Filter PCB to Inverter PCB)
Connector and wiring connection state check
Cable open check
Replace Filter PCB and Inverter PCB.
Check Point 1-1 :
Turn the power on again.
Error displayed again?
Check Point 3 : Replace Filter PCB (INV) and Inverter PCB
02-12
Trouble shooting 10
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
AMP Air Conditioning
www.ampair.co.uk | [email protected]