Trouble shooting 1
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
OK
Indicate or Display:
Refer to error code table.
YES
YES
NO
Serial Communication Error
(Serial Reverse Transfer Error)
Outdoor unit Main PCB
Outdoor unit Fan motor
1. Connection failure 2. External cause 3. Main PCB failure 4. Inverter PCB (IPM) failure
5. Filter PCB failure 6. Outdoor unit Fan motor failure
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
Check Point 2 : Check connection
Check any loose or removed connection line of
between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check connection condition in control unit.
(If there is loose connector, open cable or mis-wiring)
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198V(AC220V-10%) - 264V(10%) appears
at outdoor unit terminal L - N.
When the indoor unit cannot receive the serial signal from Outdoor unit
more than 2minutes after power ON, or the indoor unit cannot receive
the serial signal more than 15seconds during normal operation.
02-03
2-2 TROUBLE SHOOTING WITH ERROR CODE
OK
Check Point 4 : Check serial signal (Reverse transfer signal)
Check serial signal (Reverse transfer signal)
>> Check if indicated value swings between AC90V and AC270V at outdoor unit terminal 1 - 3.
>> If it is abnormal, Check the parts as follows.
- Outdoor unit fan motor (PARTS INFORMATION 5)
- Inverter PCB (IPM) (PARTS INFORMATION 6)
>> If Outdoor fan motor is abnormal, replace Outdoor unit fan motor and Main PCB.
>> If IPM is abnormal, replace it.
>> If the parts are normal, replace Main PCB.
1
2
3
L
N
RED
WHITE
BLACK
BLACK
WHITE
+
-
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание AOG60LATT
Страница 32: ...AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 33: ...2 TROUBLE SHOOTING R410A DUCT type INVERTER AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 74: ...AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 75: ...3 DISASSEMBLY PROCESS R410A DUCT type INVERTER AMP Air Conditioning www ampair co uk sales ampair co uk ...