1-5. INDOOR FAN CONTROL
1. Fan speed
( Table 5 : Standard of Indoor Fan Speed )
2. FAN OPERATION
The airflow can be switched in 4 steps such as Auto, Lo, Me, Hi, while the indoor fan only runs.
When [Auto] is selected, the indoor fan motor runs Me.
01-06
AR* G60LHTA
(Static pressure : 60Pa (Standard))
Operation
mode
Air flow
mode
Speed
(rpm)
Hi
1090
1050
900
860
780
740
420
380
420
380
Me
Lo
Heating
Intermittent
Fan
moter
1
2
1
2
1
2
1
2
1
2
S-Lo
Operation
mode
Air flow
mode
Speed
(rpm)
Hi
1090
1050
900
860
780
740
420
380
420
380
780
740
420
380
420
380
Me
Lo
Intermittent
Cooling
Fan
Dry
Fan
moter
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
S-Lo
Auto
Intermittent
S-Lo
3. COOLING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature,
as shown in Fig. 6.
On the other hand, if switched in [Hi] ~ [Lo], the indoor motor will run at a constant airflow of [Cool]
operation modes Lo, Me, Hi ,as shown in Table 5.
( Fig.6 : Airflow change - over ( Cooling : AUTO ) )
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
TR-Ts > 2°C
=
1°C > TR-Ts
2°C > TR-Ts > 1°C
=
TR-Ts > 2.5°C
=
1.5°C > TR-Ts
2.5°C > TR-Ts > 1.5°C
=
Hi mode
Me mode
Lo mode
*1
*1 : Contains a condition to the following
When the operation mode is set to Auto mode
at the start of operation.
When the setting temperature was changed.
When the operation mode was changed to Cooling mode.
When the airflow mode was changed to Auto mode.
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание AOG60LATT
Страница 32: ...AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 33: ...2 TROUBLE SHOOTING R410A DUCT type INVERTER AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 74: ...AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 75: ...3 DISASSEMBLY PROCESS R410A DUCT type INVERTER AMP Air Conditioning www ampair co uk sales ampair co uk ...