5. HEATING OPERATION
01-06
TR-Ts > - 1.5 °C
=
- 2.5 °C > TR-Ts
- 1.5 °C > TR-Ts > - 2.5 °C
=
TR-Ts > - 1 °C
=
- 2 °C > TR-Ts
- 1 °C > TR-Ts > - 2 °C
=
( Fig.7 : Airflow change - over ( Heating : AUTO ) )
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
Low mode
Med mode
High mode
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Fig. 7.
On the other hand, if switched [HIGH] [QUIET], the indoor motor will run at a constant airflow of [HEAT]
operation modes QUIET, LOW, MED, HIGH, as shown in Table 6.
4. DRY OPERATION
During the dry operation, the fan speed setting can not be changed,it operates automatically as shown in Fig. 6.
Room temperature variation which the room temperature sensor of the indoor unit body has detected.
Compressor
ON
OFF
Indoor fan
Dry air flow
S-Lo
OFF
( Fig.6 : Indoor Fan Control )
10 30
60
180
60
180
60 10
30
(SEC)
*Hi
or setting fan mode
*Lo
or setting fan mode
37°C
29°C
32°C
24°C
Indoor heat exchanger
temperature rises
Indoor heat exchanger
temperature drops
During Normal Heating operation
S-Lo
*Lower speed is selected.
6. COOL AIR PREVENTION CONTROL (Heating mode)
The maximum value of the indoor fan speed is set as shown in Fig. 8, based on the detected
temperature by the indoor heat exchanger sensor on heating mode.
When the compressor does not operate, the indoor fan motor operates [S-Lo] mode.
( Fig.8 : Cool Air Prevention Control )