13. AUTO RESTART
14. MANUAL AUTO OPERATION (When using the Wireless RC)
If MANUAL AUTO Button is set, the operation is controlled as shown in Table 14.
If the remote control is lost or battery power dissipated, this function will work without the remote control.
Operation mode
Auto changeover
Auto
Continuous (No timer setting available)
24°C
(Table 14)
Setting temp.
OFF
Economy
Fan control mode
Timer mode
15. COMPRESSOR PREHEATING
When the outdoor heat exchanger temperature is lower than 5°C and the all operation
has been stopped for 30 minutes, power is applied to the compressor and the compressor is heated.
(By heating the compressor, warm air is quickly discharged when operation is started.)
When operation was started, and when the outdoor temperature rises to 7°C or greater, preheating is ended.
When the power was interrupted by a power failure, etc. during operation, the operation contents
at that time are memorized and when power is recovered, operation is automatically resumed with
the memorized operation contents.
(Table 13 : Operation contents memorized when the power is interrupted)
Operation mode
Set temperature
Set air flow
Set air flow direction
Swing
Economy operation
Thermistor detected position
Timer mode
Wireless remote
controller
Wired remote controller
(Memory Backup : Disable)
Wired remote controller
(Memory Backup : Enable)
OFF Timer
ON Timer
WEEKLY Timer
Temperature
: Memorize
: Not memorize
*It is necessary to set on the DIP-SW1-No,6 of the wired remote controller, to enable the memory backup.
Refer to the installation manual of wired remote controller for details.
SET BACK Timer
01-15
Содержание AOCG040LBTA
Страница 3: ...R410A SLIM DUCT type INVERTER 1 DESCRIPTION OF EACH CONTROL OPERATION ...
Страница 26: ...2 TROUBLE SHOOTING R410A SLIM DUCT type INVERTER ...
Страница 59: ...3 APPENDING DATA SLIM DUCT type INVERTER R410A ...
Страница 67: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jun 2016 Printed in Japan ...