7. COMPRESSOR CONTROL
1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the Table 10.
Cooling / Dry
Heating
Minimum
Maximum
Minimum
Maximum
AOCG040LBTA
12rps
99rps
16rps
140rps
AOCG040LBTA
40rps
59rps
72rps
80rps
101rps
110rps
(Table 10 : Compressor frequency range)
2. OPEARTION FREQUENCY CONTROL AT NORMAL START UP
The compressor frequency soon after the start-up is controlled as shown in the Fig.11
(Fig.11 : Compressor control at start-up)
Time
Time
Time
Time
Time
(Frequency)
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Time
Time
Time
Time
Time
AOCG040LBTA
80sec
110sec
140sec
200sec
350sec
410sec
(Time)
Frequency
Time
6
Frequency
Time
6
3. LIMITATION OF COMPRESSOR FREQUENCY BY OUTDOOR TEMPERATURE
The minimum compressor frequency is limited by outdoor temperature as shown in the Table11.
AOCG040LBTA
24rps
18rps
12rps
16rps
(Table11 : Limitation of Compressor Frequency)
[ Cooling/ Dry ]
[ Heating ]
Under
Over
Under
Over
Under
Over
0°C
10°C
40°C
AOCG040LBTA
Under
Over
Under
Over
Under
Over
Under
Over
24rps
24rps
18rps
16rps
16rps
- 5°C
3°C
7°C
40°C
01-09