3. SLEEP TIMER
If the sleep timer is set, the room temperature is monitored and the operation is stopped automatically.
If the operation mode or the set temperature is change after the sleep timer is set, the operation is
continued according to the changed setting of the sleep timer from that time ON.
Set temperature rises
( Ts : Set temperature )
Stop of operation
Set temperature lowers
( Ts : Set temperature )
Ts
Stop of operation
In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 1 °C
It increases the setting temperature another 1 °C after 1 hour.
After that, the setting temperature is not changed and the operation is stopped at the time
of timer setting.
Ts
+1°C
+2°C
-2°C
-1°C
-4°C
-3°C
Set
60min
In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 1 °C.
It decreases the setting temperature another 1 °C every 30 minutes.
Upon lowering 4 °C, the setting temperature is not changed and the operation stops
at the time of timer setting.
Set
30min 30min 30min
01-11