01-07
Compressor
ON
OFF
Indoor fan
Setting air flow
OFF
10
30
60
180
60
180
60 10
30
(sec)
S-Lo
480rpm
( Fig 9 : Indoor Fan Control)
7. FAN CONTROL FOR ENERGY SAVING
When the air flow setting except AUTO mode, the indoor fan motor will run as shown in Fig.9.
( Factory setting)
Setting Description
Function Number
Setting Value
Disable
Enable
49
00
01
00 : When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01 : When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.