03-02
( Factory setting)
Setting Description
Function Number
Setting Value
Standard
Lower control
Slightly warmer control
Warmer control
31
00
01
02
03
1-4. Setting the Heater room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be changed as shown in the table below.
1-3. Setting the Cooler room temperature correction
( Factory setting)
Setting Description
Function Number
Setting Value
Standard
Slightly lower control
Lower control
Warmar control
30
00
01
02
03
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be selected as shown in the table below.
When using floor console installation, change the setting value to "01".
When using floor console installation, change the setting value to "01".
1-5. Setting the Auto restart
Enable or disable automatic system restart after a power outage.
( Factory setting)
Setting Description
Function Number
Setting Value
Yes
No
40
00
01
Auto restart is an emergency function such as for power failer etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, or external input device.