5. INDOOR FAN CONTROL
1. Fan speed
( Table 6 : Indoor Fan Speed )
01-05
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs.
(Hi > Me, Me > Lo, Lo > Quiet, Quiet > Soft Quiet)
Operation mode Air flow mode
Speed (rpm)
1560
1400
1240
1030
500
1560
1400
1240
1030
500
1030
500
Dry
Monitoring
Cooling
Fan
Heating
ARCG040LSTA
Hi
Me
Lo
Quiet
S-Lo
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
S-Lo
2. FAN OPERATION
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH,
while the indoor fan only runs.
When Fan mode is set at (Auto), it operates on [MED] Fan Speed.
3. COOLING OPERATION
( Fig.5 : Airflow change - over ( Cooling : AUTO ) )
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
TR-Ts > 2 °C
=
1 °C > TR-Ts
2 °C > TR-Ts > 1 °C
=
TR-Ts > 2.5 °C
=
1.5 °C > TR-Ts
2.5 °C > TR-Ts > 1.5 °C
=
High mode
Med mode
Low mode
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Fig. 5.
On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [COOL]
operation modes QUIET, LOW, MED, HIGH, as shown in Table 6.