En-9
● When function setting is “Emergency stop” mode.
[In the case of “Edge” input]
Connector
Input signal
Command
Ch1 of CNA01 or CNA02
OFF → ON
Emergency stop
ON → OFF
Normal
[In the case of “Pulse” input]
Connector
Input signal
Command
CNA01 or CNA02
Ch1
OFF → ON
Emergency stop
Ch2
OFF → ON
Normal
* All indoor units of same refrigerant system stops when Emergency stop operates.
●
When function setting is “Forced stop” mode.
[In the case of “Edge” input]
Connector
Input signal
Command
Ch1 of CNA01 or CNA02
OFF → ON
Forced stop
ON → OFF
Normal
[In the case of “Pulse” input]
Connector
Input signal
Command
CNA01 or CNA02
Ch1
OFF → ON
Forced stop
Ch2
OFF → ON
Normal
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
* When forced stop function is used with forming a remote controller group, connect the
same equipment to each indoor unit within the group.
• Selection method of functions
“Operation/Stop” mode or “Emergency stop” mode, “Forced stop” mode can be selected
with function setting of indoor unit.
●
Forced thermostat off function
[“Edge” input only]
Function
setting
Connector
Input signal
Command
60-00
Ch3 of CNA03 or
CNA04
OFF → ON
Thermostat off
ON → OFF
Normal
●
Refrigerant leak detection function (only for J-IIIL series)
[“Edge” input only]
Function
setting
Connector
Input signal
Command
60-09
Ch3 of CNA03 or
CNA04
OFF → ON
No command
ON → OFF
Refrigerant leak
(2) External output
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• Output voltage: Hi DC12V±2V, Lo 0V.
• Permissible current: 50mA
Output select
●
When indicator etc. are connected directly
Operation indicator
Error indicator
Indoor unit Fan
status indicator
connected unit
P.C.B
CNB
01
●
When connecting with unit equipped with a power supply
CNB
01
P.C.B
Connected
device 1
Connected
device 2
Connected
device 3
connected unit
Relay (locally purchased)
Operation behavior
Connector
Output voltage
Status
CNB01
External output1
Pins 1-2
0V
Stop
DC 12 V
Operation
External output2
Pins 1-3
0V
Normal
DC 12 V
Error
External output3
Pins 1-4
0V
Indoor unit fan stop
DC 12 V
Indoor unit fan operation
7. FIELD SETTING
There are 3 methods for address setting by FIELD SETTING as follows.
Set by either of the methods.
Each setting method is described (1) to (3) below.
(1) IU AD, REF AD SW settings: This section (7.1. Setting the address)
(2) Remote controller settings:
Refer to the wired or wireless remote controller manual
for detailed setting information. (Set IU AD, REF AD
SW to 0)
(3) Automatic address settings: Refer to the outdoor unit manual for detailed setting
information. (Set IU AD, REF AD SW to 0)
CAUTION
Be sure to turn OFF the power before performing the field setting.
Do not operate any switches other than prescribed, as it can cause the unit to operate
improperly or malfunction.
Use an insulated screwdriver to set the DIP switches.
7.1. Setting the address
Manual address setting method
CAUTION
Use an insulated screwdriver to set the dip switches.
IU AD
REF AD
RC AD
×10 ×1
×10 ×1
SET3
SET4
For indoor
unit address
For refrigerant
circuit address
Setting
Setting range
Type of switch
Indoor unit ad-
dress
0 to 63
Setting
example 2
IU AD×10
IU AD×1
Refrigerant circuit
address
0 to 99
Setting
example 63
REF AD×10
REF AD×1
(1) Indoor unit address
Rotary switch (IU AD ×1)...
Factory setting “0”
Rotary switch (IU AD ×10)...Factory sett
ing “0”
When connecting multiple indoor units to 1 refrigerant system, set the address at IU AD SW
as shown in the Table A.
(2) Refrigerant circuit address
Rotary switch (REF AD ×1)...Factory setting “0”
Rotary switch (REF AD ×10)...Factory setting “0”
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A for
each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
•
If working in an environ
-
ment where the wireless
remote controller can be
used, the addresses can
also be set using the
remote controller.
• If setting the addresses
using the wireless
remote controller, set
the indoor unit address
and refrigerant circuit
address to “00”.
(For information on set-
ting using the wireless
remote controller.)
* Do not set the indoor
unit address (IU AD
SW) at 64 to 99.
It may result in failure.
Table A
Address
Rotary switch
setting
Address
Rotary switch
setting
Refrigerant
circuit
REF AD SW
Indoor unit
IU AD SW
× 10
× 1
× 10
× 1
0
0
0
0
0
0
1
0
1
1
0
1
2
0
2
2
0
2
3
0
3
3
0
3
4
0
4
4
0
4
5
0
5
5
0
5
⁞
⁞
⁞
⁞
⁞
⁞
10
1
0
10
1
0
11
1
1
11
1
1
⁞
⁞
⁞
⁞
⁞
⁞
99
9
9
63
6
3
9371022635-01_IM.indb 9
08/02/2019 17:03:28